JABLOTRON FUTURA
SYSTEM DESIGN GUIDE
Page 4/16
JABLOTRON LIVING TECHNOLOGY
D es crip t ion
D es crip t ion
M
M
L
L
Cooling / heating output of complete
set including exchanger heat
recovery ( CoolBreeze)
1,5 kW - 3,8 kW / 4,9 kW****
1,7 kW - 4,4 kW / 4,9 kW****
Annual electricity consumption (AEC)
(in kWh/m
2
electric power/year)
„average“, „hot“, „cold“) at reference
flow
2,26/1,81/7,63
2,20/1,75/7,57
Annual heat savings (AHS) (in
kWh/m
2
of primary energy/year) for
individual climate zones („average“,
„hot“, „cold“) at reference flow
47/92/21
47/92/21
Exchanger
enthalpy counter-current exchanger with
humidity recovery control
enthalpy counter-current exchanger with
humidity recovery control
Summer functions
fully automatic by-pass controlled by the
temperature setpoint
fully automatic by-pass controlled by the
temperature setpoint
control
Integration in the MyJABLOTRON app, which
supports easy control of all the user
functions and settings, remote monitoring
and administration and automatic alerting
to filter replacement and error conditions.
Supplied with a wall-mounted control with
an integrated CO
2
sensor (1 piece) as
standard.
Integration in the MyJABLOTRON app, which
supports easy control of all the user
functions and settings, remote monitoring
and administration and automatic alerting
to filter replacement and error conditions.
Supplied with a wall-mounted control with
an integrated CO
2
sensor (1 piece) as
standard.
Optional equipment
CoolBreeze enthalpy heating/cooling
module, forced exhaust (boost) buttons with
operation indication; Rh, SQA, CO
2
sensors,
VAC material and distribution elements
CoolBreeze enthalpy heating/cooling
module, forced exhaust (boost) buttons with
operation indication; Rh, SQA, CO
2
sensors,
VAC material and distribution elements
* According to Czech norm ČSN EN 308
** According to Czech norm ČSN EN ISO 3744
*** According to Commission Regulation (EU) č. 1253/2014
**** Cooling output varies depending on the relative humidity and difference between indoor and outdoor temperature.
**** Heating output varies depending on the relative humidity and difference between indoor and outdoor temperature.
ANY CHANGES RESULTING FROM TECHNICAL DEVELOPMENT ARE RESERVED. WE RESERVE THE RIGHT TO CHANGE THE CONTENTS OF THE MANUAL