JABLOTRON FUTURA

INSTALLATION MANUAL

43/43

JABLOTRON LIVING TECHNOLOGY

D i m e n s i o n a l   d r a w i n g   -   d e s c r i p t i o n

D i m e n s i o n a l   d r a w i n g   -   d e s c r i p t i o n

1.  Condesate drain connection from Futura

2.  Groove, (diameter 22 mm) for CoolBreeze condensate hose

3.  Condesate drain connection from CoolBreeze

4.  When installing, keep space of at least 330 mm (distance for fitting EPP elbow)

5.  Refrigerant inlet / outlet for CoolBreeze

6.  When installing CoolBreeze, use a flange from the Futura unit

7.  When installing, keep space of at least 370 mm for condensate drain connection

8.  DN 32 hose

9.  HL138 siphon (Futura)

10.  Sewer connection

11.  T piece HT 32

12.  STY-517-1 siphon (CoolBreeze)

13.  When installing, keep space of at least 500 mm for filter change

14.  Ambient air

15.  Waste air

16.  Fresh air

17.  Indoor air

Summary of Contents for Futura

Page 1: ......

Page 2: ......

Page 3: ...gency shutdown function 12 Error alerts and their solutions 1 Alfa control panel error alerts 2 Wall mounted control panel error alerts 3 Reset to default settings 13 Maintenance 14 Annex 1 Annex 1 Un...

Page 4: ...lies with the Commission Regulation EU No 1253 2014 with regard to ecodesign requirements for ventilation units and Commission Delegated Regulation EU No 1254 2014 with regard to energy labelling of r...

Page 5: ...anical damage and harmful environmental effects and not interfere with the use of the premises where the unit will be installed The unit may be operated only by physically and mentally apt persons tha...

Page 6: ...ctional Drive type variable speed drive variable speed drive Heat recovery system type recuperative recuperative Heat recovery efficiency 91 8 91 4 Reference flow 175 m h 103 CFM 245 m h 144 CFM Elect...

Page 7: ...tion which supports easy control of all user functions and settings It enables remote monitoring system administration and provides automatic alerts for error conditions and dirty filter replacement S...

Page 8: ...llation please allow additional 70 cm 28 in of free space above the unit The following has to be available at the installation site 2 x EPP air duct connections for outdoor use and 2 x Sonotex flexi s...

Page 9: ...intake from the exterior and the air exhaust to the exterior to prevent the possibility of unwanted condensation inside the pipes For indoor air distribution use Sonotex piping with silencer The air...

Page 10: ...ds the siphon The condensate drain connection is found on the bottom of the heat recovery unit A siphon which is connected to the sewerage system must be mounted onto the coupling of the condensate dr...

Page 11: ...ing device must be connected in accordance with relevant standards and guidelines and may only be carried out by a trained service technician with appropriate electrical and refrigeration qualificatio...

Page 12: ...cts correct directional insertion of filters condensate drain functionality correct electrical connection and readiness for the operation of all technical components of the unit Any defects must be co...

Page 13: ...ure Short press filter initialization long press Bluetooth connection MyCOMPANY application retrieves serial number from the unit Configuration is saved directly in the unit X2 X3 X4 X5 X6 T1 G N D X1...

Page 14: ...Continue Figure 8 Ventilation connection check Configuring IP address Configuration of the IP address is run automatically from the DHCP server but may be set manually as well In order to configure th...

Page 15: ...l air volume and tap on the arrow in the bottom right corner to run the analysis The function will calculate maximum available air flow for each of the five ventilation levels according to the real la...

Page 16: ...tering the unit must be connected to the internet When the unit is on it logs into the preset server and maintains a permanent connection Figure 16 Registration key Log in to MyCOMPANY run device regi...

Page 17: ...oning system Max 8 1 1 4 Max 8 1 4 0 2 Figure 20 Possible zone combinations The picture above shows the number of control panels valves and buttons that can be used for each zone When configuring zone...

Page 18: ...or set the switch to the ON position when you are using a terminating resistor Figure 21 Setting zone number on Alfa control panel DIP switch 8 2 Configuration of a valve DIP switch Second it is neces...

Page 19: ...me and turn off automatically This configuration can be used for example in a bathroom If the no 5 switch on the DIP is set to the ON position the extract button will work as a switch when pressed the...

Page 20: ...how how to set valve addresses switches no 4 and 5 and supply zone switch no 6 on a valve DIP switch 5 Figure 24 Example of configuring a supply zone zone no 5 two valves supply 8 5 Extract zone confi...

Page 21: ...responding zone shown zone no 1 same as in Fig 25 First column switch no 4 shows button address Second column switch no 5 shows that the button is set as a switch ON until pressed again Third column s...

Page 22: ...ar dependence starting at 1 V see Fig 29 This setting however will not stop the system entirely The minimum power level at 0 V of input voltage corresponds to 1 of the power which is about 65 m h for...

Page 23: ...operational information is displayed on the control panel start of heating within the heating circuit temperature setpoint of the heating circuit the set heating mode manual mode time schedule vacati...

Page 24: ...assigned to the selected input see pictures below No additional configuration is needed for the Emergency shutdown input Activation of the function disconnects the contact When the emergency shutdown...

Page 25: ...door temperature below limit 8 VAV ventilation not configured properly supply Check the setting of the supply zones of the VAV ventilation 9 VAV ventilation not configured properly extract Check the s...

Page 26: ...error Change sensor Error No 2 Fan error Check cable connection Error No 3 Heat exchanger error Check cable connection Error No 4 I O board error Change I O board Error No 5 9 Unspecified 12 3 Reset...

Page 27: ...status remove front cover 2 screw dismount filter plugs and remove them remove plugs A B C D with a spatula of minimal width of 5 cm 2 in check the heat exchanger visually clean first half of valve r...

Page 28: ...aste air C Supplied air D Extracted air Description 1 Outdoor air filter 2 Terminal 3 Main board 4 Servo bypass 5 T RH waste air sensor 6 Circulation servo 7 T RH outdoor air sensor 8 IO board 9 Extra...

Page 29: ...Technical parameters Insulation thickness 25 mm 1 in R 0 65 m K W Minimal temperature 30 C 22 F Maximum temperature 140 C 284 F Operating pressure 188 to 2500 Pa Operating speed max 25 m s Bend radius...

Page 30: ...JABLOTRON FUTURA INSTALLATION MANUAL 28 43 JABLOTRON LIVING TECHNOLOGY 14 3 Annex 3 Wiring diagram 3a Internal wiring diagram of Futura...

Page 31: ...MANUAL 29 43 JABLOTRON LIVING TECHNOLOGY 1 Power supply 24 V 2 Heat exchanger 3 Supply fan 4 Extract fan 5 Drying servo 6 Outdoor air sensor 7 Bypass servo 8 Waste air sensor 9 Fresh air sensor 10 Ex...

Page 32: ...N FUTURA INSTALLATION MANUAL 30 43 JABLOTRON LIVING TECHNOLOGY In Out 230 V AC 5 4 2 3 1 3b CoolBreeze wiring diagram 1 Outdoor unit 2 CoolBreeze 3 T RH extract air sensor 4 Evaporator 5 NTC evaporato...

Page 33: ...put connection LED output for LED boost indication 24 V 20 mA max BST boost button IN2 IN1 analog input 0 10V or digital input for potential free contact against GND GND common ground X6 AA bus connec...

Page 34: ...control panel 1 8 pieces 2 VarioBreeze room by room ventilation button 1 16 pieces 3 CO2 sensor 1 8 pieces 4 VarioBreeze room by room ventilation valve 1 64 pieces 5 NTC outdoor temperature sensor 6...

Page 35: ...tivated by connecting the contact Example of analog input connection for emergency shutdown Mode is activated by disconnecting the contact Connecting the contact deactivates the mode Example of 0 10 V...

Page 36: ...simultaneously as this will cause irreparable damage to the system 14 6 1 Connecting Alfa control panel via RS 485 bus ALFA I N O U T 14 6 2 Connecting Alfa control panel via AA BUS Only one control...

Page 37: ...35 43 JABLOTRON LIVING TECHNOLOGY 14 7 Annex 7 Configuration of control panel and CO2 sensor Modbus RTU addresses 14 7 1 Alfa control panel 1 2 3 OFF 1 ON 2 3 OFF 2 ON 1 3 OFF 1 2 ON 3 OFF 3 ON 1 2 OF...

Page 38: ...unted control panel with CO2 sensor or a separate CO2 sensor Make sure to always activate via DIP switch a terminating resistor to the last device control panel or sensor in the line Always activate t...

Page 39: ...of control panel DIP switches CO2 sensor DIP switches and valve DIP switches for max 8 ventilation zones Control panel and CO2 DIP switch combinations are stated in columns 2 4 Valve DIP switch settin...

Page 40: ...ches and boost button DIP switches for max 8 ventilation zones Valve DIP switch combinations are stated in columns 2 5 according to the actual number of valves within the given zone Boost button DIP s...

Page 41: ...erence flow rate 175 m h 245 m h Reference pressure difference 50 Pa 50 Pa SPI 0 34 W m h 0 33 W m h Declared maximum internal and external leakage rates 2 5 2 5 2 5 2 5 Position and description of vi...

Page 42: ...ING TECHNOLOGY 14 10 Annex 10 Energy labels 2017 1254 2014 46 dB I II 3 JABLOTRON LIVING TECHNOLOGY CZ s r o Futura A A B C D E F G A 250 m h 2017 1254 2014 46 dB I II 350 m3 h JABLOTRON LIVING TECHNO...

Page 43: ...TALLATION MANUAL 41 43 JABLOTRON LIVING TECHNOLOGY 14 11 Annex 11 Dimensional drawing Main dimensions including CoolBreeze indoor unit 133 3x243 830 910 1274 169 6 73 10 110 370 111 247 364 260 1 2 3...

Page 44: ...JABLOTRON FUTURA INSTALLATION MANUAL 42 43 JABLOTRON LIVING TECHNOLOGY 200 18 59 444 60 33 524 13 14 15 16 17...

Page 45: ...space of at least 330 mm distance for fitting EPP elbow 5 Refrigerant inlet outlet for CoolBreeze 6 When installing CoolBreeze use a flange from the Futura unit 7 When installing keep space of at lea...

Page 46: ......

Page 47: ......

Page 48: ......

Reviews: