background image

JABLOTRON

ALARMS

a.s.

Pod

Skalkou

4567/33

46601

Jablonec

n.

Nisou

Czech

Republic

www

.jablotron.com

||

|

JA-111ST Bus combined smoke and heat detector

JA-111ST  Bus combined smoke and heat detector

1 / 2

MLW55307

The JA-111ST is a component of the 

JABLOTRON JA-100 

alarm 

system. It is used to detect fire hazards in the interior of residential or 
commercial buildings. The product is not designed to be installed in 
industrial premises. The detector is powered via the control panel digital 
bus (EN 54-7; EN 54-5). When the detector is used with inserted 
batteries (3x 1.5 V AA) from which it can be powered, it can continue 
operating as a stand-alone detector when the 12 V power supply 
is disconnected (EN 14604).

The detector indicates fire hazard using the built-in LED indicator and 

acoustic signalling.

The JA-111ST consists of two independent detectors – an optical 

smoke detector and a heat detector. The optical smoke detector works 
on the principle of scattered light. It is very sensitive to large dust 
particles which are present in dense smoke. It is less sensitive 
to smaller particles generated by the combustion of liquids such 
as alcohol. That is why the fire detector also contains a built-in heat detector 
which has a slower reaction but is much better at detecting fire which 
generates only a small amount of smoke.

Detector range and location

The smoke detector must be installed so that any smoke easily drifts 

into the detector owing to natural thermal currents, e.g. on the ceiling. It is 
suitable for residential buildings but not suitable for free spaces, outdoor 
environments or interiors with extremely high ceilings (above 5 m) 
where fire by-products can disperse over a large area – the smoke 
would not reach the detector position.

The detectors should be installed by a trained technician with a valid 

manufacturer’s certificate.

Detectors should be installed in the building according to the project 

documentation. If such documentation is not available, their position
should comply with the effective standards for fire alarm signalling 
systems.

The detector must always be placed in the section leading to the exit 

of the building (escape route), see

Fig. 1

. If the building has a floor area 

greater than 150 m

2

, installation of an additional detector in some other 

suitable place is required, see 

Fig.2

.

1. kitchen, 

2. living room, 

3. – 6. bedrooms

y

/

basic coverage

{

/

recommended coverage

Fig 1

Fig 2

Fig 3

In multi-storey flats and family houses the detector should be 

installed above the stairs. It is recommended to place additional 
detectors in rooms where people sleep. See 

Fig 3

.

Installation on level ceilings

Place the detector in the centre of the room if possible.

The detector 

must not be recessed into the ceiling due to the possible existence 
of a cool air layer on the ceiling. Never place the detector in the 
corner of the room (always keep at least 0.5 m distance from the 
corner - see Fig 4).

There is an insufficient circulation of air in the 

corners.

Installation on sloping ceilings

If the ceiling is not suitable for mounting on a level surface (e.g. a 

room under a roof ridge), the detector can be installed as in Fig. 5. 

Fig 1

0,9 m

Fig 2

centre of the room, best location

acceptable location

Walls, partitions, barriers and lattice ceilings

The JA-111ST detector must not be installed closer than 0.5 m 

from any wall or partition.

A narrow room with a width of less than 1.2 m

requires the detector(s) to be placed at a distance of at least one third of the 
room’s width away. In a case when a room is separated into sections with 
walls, semi partition walls or furniture which do not reach the ceiling, the 
space is considered as a fully separated if the gap between the top of 
these and the ceiling does not exceed 0.3 m are performed as a single 
rooms. A free space of at least 0.5 m is required under and around the 
detector. Any irregularities of the ceiling (e.g. girders) exceeding 5 % of the 
ceiling height should be considered a wall and the above mentioned limitations 
should apply.

Ventilation and air circulation

The detectors must not be installed directly by ventilation or air 

conditioning vents.

In the case of air being supplied through a 

perforated ceiling, each detector must be placed so that no perforation 
hole occurs within 0.6 m of the detector.

Avoid installing the detector in the following locations:

x

places with poor air circulation (niches, corners, apexes of 
A-shaped roofs, etc.)

x

places exposed to dust, cigarette smoke or steam

x

places with over-intense air circulation (close to ventilators, heat 
sources, air conditioning outlets, etc.)

x

in kitchens and other cooking places (because steam, smoke or oily 
fumes can cause false alarms or reduce detector sensitivity).

x

beside fluorescent lights or energy-saving light bulbs (electrical 
interference can cause a false alarm)

x

in areas with lots of small insects

Warning:

Most false alarms are caused by improper detector 

location.

See CEN/TS 54-14 standards for detailed installation guidelines.

Installation

When installing the detector, abide by the procedures recommended 

in the previous paragraphs.

Fig 3: 1 – detector cover opening; 2 – detector cover closing; 

3 – optical status signalling; 4 – arrow showing where to insert the detector; 

5 – bus terminal; 6 – production code; 7 – battery holders

1.

Open the detector cover

, by turning it anti-clockwise 

(1)

2.

Push the bus cable through the base and attach the base

to the 

selected place using screws.

3.

Connect the bus cable.

4.

When the device is switched on, the yellow LED on the PCB 
inside the detector starts flashing repeatedly to indicate that 
the detector has not been enrolled into the system.

When connecting the detector to the 
system digital bus, always switch the 
power off.

Reviews: