background image

JA-150ST Wireless combined smoke and heat detector

JA-150ST Wireless combined smoke and heat fire detector

2 / 2

MLW51707

Instructions:

1. Open the detector cover, by turning it anti-clockwise (1).
2. Attach the removed plastic base to the desired place with screws.
3. Set the configuration jumpers (6) according to the table below.

4.

Proceed according to the control panel installation manual. Basic 
procedure:

a.

Go to the 

F-Link

program, select the required position in 

the 

Devices

window and launch 

Enrollment mode

by 

clicking on the 

Enroll

option. 

b. Insert all batteries into the detector, an enrollment code is 

sent to the system – sending is confirmed with a short flash 
of the LED indicator (3).

5. Insert the detector into the plastic base. The detector can be 

inserted into the plastic base only in one position, which is marked 
with arrows (4) on both plastic parts, provided that all three 
batteries are inserted. Close the detector cover by turning 
it clockwise (2). When the detector is fully secured to the base, 
a control LED lights up (3), which indicates an automatic detector 
test. During this period of time, the detector doesn’t detect anything.
The test ends when the LED shuts down (3), the detector becomes 
fully operational. A possible detector fault may be indicated, see the 

Fault indication

chapter.

Note: 

The detector can also be enrolled into the system by entering its serial number 

(5) in the F-Link program or on a keypad (or using a bar code scanner). 
All numbers stated under the bar code shall be entered (1400-00-0000-0001).

Detector settings

The detector properties can be set with configuration jumpers.

1

ON

Memory disabled

2

OFF

Smoke(EN 54-

7) or heat (EN 

54-5)

OFF

Memory enabled

3

OFF

ON

OFF

2

OFF

Smoke only

(EN 54-7), (not 

heat)

3

ON

2

ON

Heat only (EN 

54-5) (not 

smoke)

3

OFF

2

ON

Smoke and 

heat (both 

conditions at 

the same time)

3

ON

Jumper 1 MEM

- Signalling the alarm memory. The signalling LED 

remains active for 24 hours after the reason for the alarm ceases to 
exist.

Jumper 2 and 3 TEMP and SMOKE

- The combination of these 

configuration jumpers defines how the detector will react to smoke and
heat.

It’s possible to change the system’s reaction to something other than 

Fire using the 

F-Link

program. This setting is in the 

Reaction

options

in the 

Devices

window.

Warning:

This device cannot be considered a fire detector when 

it’s configured to a different reaction. Upon detector activation, the
system signals accordingly to the settings of the control panel. The 
detector will always signal activation by smoke or heat with 
a quickly flashing red LED regardless of the configured reaction 
and the control panel status (set/unset/service).

Fire alarm

Optical detector:

When smoke enters the detector, an alarm is 

triggered, and it is signalled with a rapidly flashing red LED light
(approx. 8 times per second). The indication lasts until the room is 
ventilated (thus also ventilating the detector’s detection chamber).

Heat detector:

When the temperature rises above a set limit, an 

alarm is triggered, and it is signalled with a rapidly flashing red LED 
(approx. 8 times per second). The indication lasts until the temperature 
drops (e.g. when the room is ventilated).

Alarm memory: 

If enabled, 

LED alarm indication

continues 

flashing slowly (approx. 4 times per second) for a further 24 hours after 
the alarm stops. The indication can be terminated by opening the 
detector cover by turning it anti-clockwise and activating the tamper 
sensor.

WARNING! 

The control panel must be switched to Service 

mode otherwise a Tamper alarm will be triggered.

Tamper alarm:

When the detector cover is opened, the tamper 

alarm is activated unless the control panel is in Service mode.

Detector testing and maintenance

Functionality of the optical part of the detector can be tested with a 

test spray for smoke detectors. The functionality of the heat part can be 
tested with a hairdryer. If the detector is configured to both conditions, 
it’s necessary to conduct both spray and hairdryer tests at the same 
time. The test should be carried out once in 30 days. The detector’s 
cover should be cleaned regularly from cobwebs and dust. No 
additional maintenance is necessary.

Warning: never test the detector with fire inside the building.

Battery replacement

The system sends a report automatically when the battery is low. 

Optical indication then flashes briefly once every 30 seconds. 
Remember to switch the system to Service mode before changing the 
batteries otherwise a tamper alarm will be triggered. It is always 
essential to replace all three batteries. Use the same type and the 
same brand for all of them. Wait for 90 seconds in order to let the 
detector’s circuitry discharge before inserting new batteries.

Fault indication

The detector checks its functionality. When a fault is detected, LED 

indication immediately flashed 3 times and then briefly 3 times every 30 
seconds (a failure of the automatic functionality test is signaled the 
same way, see the 

Installation

chapter). The error found may be 

caused by a fault of the detection chamber, the temperature of the 
environment being out of the operating temperature range or other 
faults of the detector.  

An operating temperature range fault will disappear the 

moment the temperature of the environment turns back to normal.

Other faults found are indicated as a fault even after their cause 

has gone. The fault indication can be stopped by the functionality 
test. The functionality test is triggered by opening the detector 
cover (fig 6-1), removing the lower plastic part and putting it back 
(fig 6-2). If this test results in a fault, send the detector to the repair 
service.

WARNING! 

The control panel must be switched to Service mode 

otherwise a Tamper alarm will be triggered.

The detector will alert you in case of low batteries by an LED flashing 

once every 30 seconds.

Technical specifications

Power

3x LR6 (AA) type alkaline batteries, 1.5 V

Warning: batteries are not included  

Typical battery lifetime

approx. 3 years

Communication band

868.1 MHz, Jablotron protocol

Communication range

approx. 300 m (unrestricted area)

Dimensions

diameter 126 mm, height 50 mm

Weight

142 g (without batteries)

Smoke detection

optical light scattering

Smoke detector sensitivity

m = 0.11 - 0.13 dB/m pursuant to EN 54-7

Heat detection

class A2 according to EN 54-5

Alarm temperature

+60 °C to +70 °C 

Operating temperature range

-10 °C to +80 °C

Complies with

EN 54-5, EN 54-7, EN 54-25

Also complies with

ETSI EN 300220, EN 50130-4

EN 55022, EN 60950-1

Can be operated according to

ERC REC 70-03

15    1293-CPR-0508

JABLOTRON ALARMS a.s. hereby declares that the JA-150ST is in a compliance 
with the relevant Union harmonisation legislation: Directives No: 2014/53/EU, 
2014/35/EU, 2014/30/EU, 2011/65/EU. The original of the conformity assessment 
can be found at www.jablotron.com - Section Downloads.

Note:

Although this product does not contain any harmful materials 

we suggest you return the product to the dealer or directly to the 
producer after use. 

Reviews: