Alarm system JA-65 MAESTRO 

- 5 - 

MFM53003 

 

2. Configuration of the control panel 

 

The metal case of the JA-65K control panel is 
shipped from the factory with a built-in power 
supply unit and the main board. To be able to 
work as an alarm system, it should be equipped 
with interface modules (R, H, X, GSM) in the 
following way: 

• 

open the case and remove the cover   

• 

disconnect the power unit cable from the 
main board connector K5 

• 

unscrew the module platform (screw on 
the left side) 

• 

open the platform and remove it from the case 

• 

attach the desired modules to the positions shown in the 
previous diagram 

• 

connect the modules' cables to the main board in the 
following way: 

60GSM or 65X = K1 

65R = K2 

65H = K3 (if two 65H modules are used, connect the 
left module cable to the right 65H module and the 
right module cable to the main board's K3 connector) 

 

3. Control panel installation 

 

The control panel’s case is designed to be attached to the wall, 
or it can be partly installed into the wall. The rectangular hole on 
the back side is for cable routing. The hole matches a KT-250   
standard junction box. This allows easy specification  on how to 
prepare cables in a house before an alarm system installation. 

• 

If the 

65R radio-communicating module

 is used, keep in 

mind that the  

antenna will need about 20 cm of 

clearance.

 The 65R  module comes with a rubber antenna, 

but it can also be used with an external antenna, model AN-
01. The working range of the wireless accessories  is about 
100 meters under optimal conditions. However, building 
materials can absorb or obstruct radio signals  and 
communication can also be effected by interference from 
other radio signals. For these reasons, you should anticipate 
a shorter working range for indoor installations.  

• 

Route all the cables

 to the control panel (power, input 

loops, outputs, telephone line etc.) before you attach the 
case to the desired location. 

Note:  if you install the case in the wall, the hinges for both the 

cover & module mounting platform should not be placed  within 

the wall. 

 

3.1. Power cable wiring 

 

The power cable should be connected only by a licensed 

electrician. 

The control panel is an electrical safety class II. 

device with double insulation and power to its power unit must 
be wired with double insulated two core power cord. No power 
wire should be connected to the metal case.

  

Instructions:  

• 

use flexible 2 core (size from 0.75 to 1.5 mm

2

) double 

insulated power cord. The system should not share a fuse 
(10 A max) with any other household item. The fuse is used 
as a circuit breaker too. 

• 

Attach the cable firmly to the board using the metal brackets. 
Before you tighten the brackets, check that the wires are 
tightly screwed in the terminals L and N and be sure that the 
wires are not longer than shown in the diagram. 

• 

Check connection of the power unit cable to the connector 
K5 on the main board. 

 

4. Antenna of the JA-65R module 

 

If the JA-65R module is installed, it will be possible to enroll wireless 
detectors, controllers, a JA-60A siren, output modules and another 
wireless subsystem if required. Enrollment is described in the part 
11.1. The 65R module must be equipped with an antenna. 

 

4.1 Rubber antenna use in the control panel  

 

There is a hole on 
the top of the control 
panel case (remove 
the plastic cap) for 
the rubber antenna. 
The rubber antenna 
is supplied with the 
65R module. Install 
the antenna after 
the module 
mounting platform is 
inserted and 
screwed inside the 
control panel case. 
Attach the antenna to the 65R board using  a screw as shown in 
the diagram. The antenna must not be obstructed by any large 
metal object. 

 

4.2 External antenna use 

 

An optional external antenna, model AN-01, can be used with 
the 65R module. This antenna has a connector, which fits the 
connector on the 65R module. If you use the external antenna, 
the rubber antenna should not be installed. The AN-01 antenna 
has a small plastic ring on its end, used to  hang it from the wall. 
Its active part (from the plastic ring to the coil) should be 
installed vertically and should not be obstructed by any large 
metal object. The antenna can be located behind furniture, etc. 

 

 

5. Connectors and terminals of the main 
board 

 

In addition to the interface module connectors  (K1, K2 and K3) 
the main board has the following connectors: 

K5 - power supply connector:  

the cable from the power unit is 

connected to this connector. 

Do not manipulate with the 

connector when it is powered.

 

K4, K6 - digital data jacks for the JA-60E keypad(s) and/or 
for a PC interface cable. 

Up to five JA-60E keypads can be 

connected to a JA-65 and the maximum length of the cable can 
be 500 meters. We recommend use of a CT-04 cable and RJ-44 
(Jablotron) crimping connectors to make the keypad cables. The 
digital data is also available on the terminals: see the  following 
description. 

Summary of Contents for MAESTRO JA-65

Page 1: ...JA 65 MAESTRO Alarm system installation manual...

Page 2: ......

Page 3: ...audible indication 12 11 19 Arming and disarming chirps with hard wired siren 12 11 20 Siren alarm in Disarm Partial arming 12 11 21 Wireless siren alarm 12 11 22 Indication of system problems when a...

Page 4: ...ireless output modules Hard wired input module JA 65H has 8 input loops with programmable triggering NC balanced or double balanced and programmable reactions Up to two JA 65H hard wired input modules...

Page 5: ...e should be connected to the metal case Instructions use flexible 2 core size from 0 75 to 1 5 mm 2 double insulated power cord The system should not share a fuse 10 A max with any other household ite...

Page 6: ...nal siren output In the normal mode it has the U terminal voltage In the alarm mode it has a GND terminal potential Connect an ordinary external siren to U and SIR terminals max load 0 7 A A back up s...

Page 7: ...ed backup period a 12V back up battery from 1 3Ah to 45Ah can be used instead A battery larger than 7Ah must be installed in an external case and the case must be equipped with tamper protection The c...

Page 8: ...module only No code requested effects F4 F8 F9 30x 301 YES 300 NO YES Partial Home arming enabled 31x 311 YES 310 NO YES Siren alarm enabled 32x 321 YES 320 NO YES Exit delay audible indication enabl...

Page 9: ...its enrollment signal The siren will send the signal only if it has no current communication with any other control panel This protects you from enrolling your neighbor s siren Enrollment is complete...

Page 10: ...ice message and telephone numbers of the built in dialer If the changes are enabled then programming sequences for number programming voice message recording and dialer testing are accessible in the U...

Page 11: ...panel was enrolled to position c3 scroll to this position in the enrolling mode and holding key 2 will erase the master control panel as a controller 11 12 Enrollment of the control panel to a UC 2xx...

Page 12: ...s after arming if any component of the system is not ready for arming Cause of the problem for example permanently triggered detector lost communication etc will remain displayed on the keypad If the...

Page 13: ...en to enter the programming mode SC 6060 MC 1234 must be set F0 6060 1234 Factory default setting disabled Note it has no influence on the user mode entering F0 MC 11 30 Addressing of wireless detecto...

Page 14: ...ed wireless controller or siren signal receiving will be similarly indicated Some detectors JA 60P JA 60N JA 60B etc have an extra testing mode which is usually activated for 5 minutes after the detec...

Page 15: ...amples There is a comprehensive help file in the Comlink program virtual control panel access complete events list item testing window RF signal oscilloscope programming dialogs map of the system show...

Page 16: ...distributor for advice local hot line number 17 Possibilities to extend the system The JA 65 alarm system is a kit which can be tailor configured according to the size of the house or the needs of th...

Page 17: ...e outputs PgX PgY Chime Fire Arm Panic Alarm Door Home AC failure Phone siren output 12 V 0 7 A Wireless outputs module 65R transmits signals for siren and PgX PgY data for UC 2xx receivers Events mem...

Reviews: