background image

Alarm system JA-65 MAESTRO 

- 6 - 

MFM53003 

1,2,3,4

 - digital data terminals (see K4, K6) provide an option to 

use standard cable for the wiring of JA-60E keypads. The 
keypads are also equipped with both  jacks and terminals.

  

 

The following terminals are on the bottom side of the 

main board: 

 

TMP

 

a pair of terminals to connect the tamper switch of an 
external device (for example: a wire operated outdoor 
siren,   OS-300). In normal use, these terminals should be 
connected together via a 2k2 resistor. Triggering of this 
loop has the same effect as control panel tampering (a 
change of ±30% or more of the End Of Line resistor will 
trigger the input). 

PGX

 

is an output (transistor switching to GND, max. 12V, 
100mA). The function of this output is determined by the  
setting in the programming mode (see 11.6).  The control 
panel also wirelessly transmits the  PGX signal and unit 
UC-216 or UC-222 can be used as a remote output of this 
signal. 

PGY

 

is an output (transistor switching to GND, max. 12V, 
100mA). The function of this output is determined by the  
setting in the programming mode (see 11.6).  The control 
panel also wirelessly transmits the  PGY signal and unit 
UC-216 can be used as a remote output of this signal. 

C

 

is a common contact of the alarm output relay, max. load 
60V / 1A. The relay is turned on during any alarm of the 
control panel. 

NC

 

is a normally closed contact of the alarm output relay. 

NO

 

is a normally open contact of the alarm output relay. 

GND

 

is a common ground terminal of the power output (-). This 
terminal is also available on 65H modules. 

SIR

 

is an external siren output. In the normal mode it has the 
+U terminal voltage. In the alarm mode it has a GND 
terminal potential. Connect an ordinary external siren to 
+U and SIR terminals (max. load 0,7 A). A back up siren 

charging input should be connected to the GND and the 
SIR terminals (during an alarm, the charging will 
temporarily halt). The siren can also be used for sounding 
arming and disarming chirps and as an audible indicator 
while  in the testing mode. 

+U

 

is a back up power output  for external items (detectors 
etc.). The max. permanent current is 0.7 or 1.2 A for max. 
15 min (not more then one cycle per hour). This output is 
fused and supervised by the control panel. If it is 
overloaded, a control panel failure will be indicated (fault 
C). The muU terminals are also available on the JA-
65H hard-wire modules for easier wiring. All +U terminals 
are connected in parallel to the +U terminal of the main 
board.

 

 

6. The JA-65H hard wired input module 
terminals 

 

Up to two 65H  modules can be used in the control panel. The 
module with its cable connected directly to the main board 
provides zone inputs 1 to 8. If the second module is installed it 
will provide zone inputs 9 to 16. The 65H module has the 
following terminals:  

1 to 8 

zone inputs

 

– Normally, detector outputs are wired here: 

see examples of wiring in diagram. For each input it is 
possible to program its method of triggering: Normally 
Closed loop, balanced 

 

 loop (10k

or double balanced 

loop (2x 10k) and the type of reaction of the system 
(see section 11.2). 

COM 

Four common terminals to close (balance) the input 
loops 

GND 

ground (negative pole) of the power supplier

  

+U 

backup power output for external devices (detectors etc.), 
max. total consumption form all +U terminals in the control 
panel can be 0,7 A.   

 

 

 

 

Summary of Contents for MAESTRO JA-65

Page 1: ...JA 65 MAESTRO Alarm system installation manual...

Page 2: ......

Page 3: ...audible indication 12 11 19 Arming and disarming chirps with hard wired siren 12 11 20 Siren alarm in Disarm Partial arming 12 11 21 Wireless siren alarm 12 11 22 Indication of system problems when a...

Page 4: ...ireless output modules Hard wired input module JA 65H has 8 input loops with programmable triggering NC balanced or double balanced and programmable reactions Up to two JA 65H hard wired input modules...

Page 5: ...e should be connected to the metal case Instructions use flexible 2 core size from 0 75 to 1 5 mm 2 double insulated power cord The system should not share a fuse 10 A max with any other household ite...

Page 6: ...nal siren output In the normal mode it has the U terminal voltage In the alarm mode it has a GND terminal potential Connect an ordinary external siren to U and SIR terminals max load 0 7 A A back up s...

Page 7: ...ed backup period a 12V back up battery from 1 3Ah to 45Ah can be used instead A battery larger than 7Ah must be installed in an external case and the case must be equipped with tamper protection The c...

Page 8: ...module only No code requested effects F4 F8 F9 30x 301 YES 300 NO YES Partial Home arming enabled 31x 311 YES 310 NO YES Siren alarm enabled 32x 321 YES 320 NO YES Exit delay audible indication enabl...

Page 9: ...its enrollment signal The siren will send the signal only if it has no current communication with any other control panel This protects you from enrolling your neighbor s siren Enrollment is complete...

Page 10: ...ice message and telephone numbers of the built in dialer If the changes are enabled then programming sequences for number programming voice message recording and dialer testing are accessible in the U...

Page 11: ...panel was enrolled to position c3 scroll to this position in the enrolling mode and holding key 2 will erase the master control panel as a controller 11 12 Enrollment of the control panel to a UC 2xx...

Page 12: ...s after arming if any component of the system is not ready for arming Cause of the problem for example permanently triggered detector lost communication etc will remain displayed on the keypad If the...

Page 13: ...en to enter the programming mode SC 6060 MC 1234 must be set F0 6060 1234 Factory default setting disabled Note it has no influence on the user mode entering F0 MC 11 30 Addressing of wireless detecto...

Page 14: ...ed wireless controller or siren signal receiving will be similarly indicated Some detectors JA 60P JA 60N JA 60B etc have an extra testing mode which is usually activated for 5 minutes after the detec...

Page 15: ...amples There is a comprehensive help file in the Comlink program virtual control panel access complete events list item testing window RF signal oscilloscope programming dialogs map of the system show...

Page 16: ...distributor for advice local hot line number 17 Possibilities to extend the system The JA 65 alarm system is a kit which can be tailor configured according to the size of the house or the needs of th...

Page 17: ...e outputs PgX PgY Chime Fire Arm Panic Alarm Door Home AC failure Phone siren output 12 V 0 7 A Wireless outputs module 65R transmits signals for siren and PgX PgY data for UC 2xx receivers Events mem...

Reviews: