TP-82IR wireless thermostat with IR sensor 

1 / 2 

MKL53202 

The TP-82IR wireless thermostat  with IR sensor

The TP-82IR is an indoor thermostat which can be used to set and 

measure the temperature in a room. Temperature adjustment can be 

performed simply by turning the setting knob. This knob can be locked 

to avoid  accidental setting. The thermostat does not use any 

programmed scheduling. The following features are also available: 

 

Anti-freeze protection

  –  any drop in temperature under the 

(configurable) 

AL Lo

  value is detected and signalled to the 

receiver. 

 

Floor temperature detection

 – the thermostat is equipped with an 

IR sensor. This is especially suitable for under-floor heating control 

–  using the IR-measured temperature floor heating regulation can 

be performed with higher precision and allows for a comfortable 

floor temperature with no additional risk of damaging the floor. 

 

When combined with an Oasis

  wireless security system 

(Jablotron), the following are possible:  

o

  Switching the heating ON and OFF remotely (by mobile 

phone, remote control or Internet). 

o

  Disabling the heating when windows are open. 

o

  Informing the user about heating faults and frost threats (if 

the temperature drops below a pre-configured value a warning 

SMS is sent). 

o

  Informing on the occurrence of fire (when the temperature is 

above a pre-configured value). 

The thermostat is compatible with AC-82, AC-83, AC-8014 receivers 

and GD-04 + GD-04R. 
 

 

 

 

 

 Installation  

The TP-82IR should be mounted in a dry indoor location. Choose a 

mounting location about 1.5 meters above  the floor in an area with 

good air circulation. The view of the IR sensor on the bottom must be 

direct and must not be shielded by any object – see the picture. Avoid 

places with draughts, dead air spots and radiant heat from the sun or 

appliances. 

1.  Release the upper cover by pressing the plastic tab on the bottom 

side of the housing 

2.  Mount the back part on to the desired location. 

3.  Insert the battery (the polarity is marked on the holder). 

4.  Close the thermostat. 

 Enrollment 

Install and connect the receiving unit to the heating system. If the 

receiving unit was purchased separately then the thermostat must be 

enrolled to it –  enter enrollment mode on the receiving unit (see its 

manual) and either enter the adjustment menu or connect the battery 

to the thermostat  (both operations cause an enrollment signal to be 

sent). 

 Configuring the fixed parameters 

The thermostat works with the following temperature thresholds:  

t Lo

 

(economic),

 t Hi

 (comfort), 

AL Lo

 (fault/freeze), 

FL Lo

 (floor low 

temperature) and 

FL Hi 

(floor high temperature). Each of the 

parameters is configurable within a corresponding temperature range – 

see the table below. 

You can enter the adjustment menu by keeping the knob pressed for 

10 seconds. Scrolling the menu is done by turning the knob. The 

display will show temperature parameter names – see the table below. 

The currently displayed parameter can be adjusted by pressing the 

knob briefly, turning the knob until the desired temperature is 

displayed, and confirming the setting by re-pressing the knob (this will 

also cause a return to the menu so that you can configure other 

parameters immediately). The adjustment menu is escaped from by 

pressing the knob while 

OK

  is displayed or automatically after 30 

seconds. The parameter ranges are restricted according to the table. 

 

Parameter 

Adjustment 

range 

Factory  Description 

SPAN 

0.1°C;0.2°C;0.5°C 

0.2°C 

Hysteresis for 

switching 

t Lo 

+6°C to +40°C* 

6°C 

Economical 

temperature 

t Hi 

+6°C to +40°C* 

40°C 

Maximal temperature 

FL 

On/Off 

On 

Floor sensor ON/OFF 

FL Lo 

+6°C to +40°C* 

22°C 

Lower  

floor-temperature 

threshold 

FL Hi 

+6°C to 40°C* 

27°C 

Upper  

floor-temperature 

threshold 

FL t 

Current temperature of the floor (displayed after 

pressing the knob) 

AL Lo 

-9°C to +20°C 

3°C 

Critically low 

temperature 

AL Hi 

+30° to +70°C 

60°C 

Critically high 

temperature 

Corr 

±

1°C 

Correction 

 

t Lo

 to 

t Hi

 and 

FL Lo

 to 

FL Hi

 must be valid ranges: 

t Lo

 must not 

be greater than 

t Hi

  and 

FL Lo

 must not be greater than 

FL Hi

 

Adjustment ranges as depicted on a coordinate axis: 

Temperature regulation range

AL Lo

t Lo

FL Lo

t Hi

FL Hi

20

9

AL Hi

30

 

 

Temperature accuracy adjustment:

  The thermostat allows you to 

configure the hysteresis –  the accuracy to which the temperature is 

regulated. The setting is done via the 

SPAN 

item in the adjustment 

menu (proceed the same way as with the threshold parameters 

mentioned above). Turning the knob lets you select one of the 

following  accuracy  ranges:  ±0.1˚C,  ±0.2˚C  or  ±0.5˚C  (the  factory 

default setting is ±0.2˚C).

 

Example: 

I

f the accuracy is adjusted to ±0.5˚C and the temperature is 

set  to  24˚C,  the  thermostat  switches  the  heating  on  when  the 

temperature  drops  below  23.5˚C  and  it  switches  it  off  if  the 

temperature goes above 24.5˚C.

 

In reality the temperature scatter can 

be slightly higher because of the temperature persistence of the room.

 

Warning: too high an accuracy can cause the heating to turn on 

and off too frequently. 

Temperature measurement correction:

  Possible temperature 

measurement offsets can be corrected via the 

Corr

  item in the 

adjustment menu. The range of adjustable corrections is 

±

1°C.

 

 Manual operation 

  When not being handled, the thermostat shows the  current 

temperature in the room. 

 

By turning the knob the desired temperature can be set

 from 

t Lo

 

to 

t Hi

 (during setting, a hand symbol is shown on the display). If 

the temperature cannot be set, see “Locking the thermostat”. 

Setting the 

t Lo

 and 

t Hi

 limits allows the installer to prevent the 

regulated temperature from being set to undesirably high or low 

values by manual operation. 

Example: 

If t 

Lo  =  +15°C  and  t

 

Hi  =  +22°C  then  the  regulation 

temperature  can  only  be  set  within  the  range  of  +15  to  +22°C 

(unless the adjustment menu is entered).

 

  If you stop turning the knob the current temperature in the room will 

be displayed again (3 seconds after the last movement of the 

knob). 

  If the 

current temperature is lower than the desired 

temperature minus the hysteresis

, the thermostat will switch the 

heating on (a symbol of wavy lines will appear on the display). 

  If the 

current temperature is higher than the desired 

temperature plus the hysteresis

, the thermostat will switch the 

heating off (the symbol of wavy lines will disappear). 