3 HEAT / 2 COOL DUAL FUEL
Switch Settings
Sw1 = ON
(Heat Pump)
Sw2 = ON
(Multi-stage)
Sw3 = ON
(Dual Fuel)
Sw4 = Reversing Valve
(OFF = ‘O’)
(ON = ‘B’)
Sw5 = ON
(Thermostat Controls Fan)
Sw6 = User Preference
(OFF = Non-Programmable)
(ON = Programmable)
Sw7 = User Preference
(OFF = 4 Schedules per Day)
(ON = 2 Schedules per Day)
Sw8 = OFF
(4 Minute Short Cycle Protection)
If an outdoor sensor is used and High or Low Balance Point control is required, set HB and LB in the
Advanced Installer menu.
IMPORTANT:
W2
Y2
W1
O/B
Y1
G
R
24
24C
B
A
T
T
REV
VALVE
FAN 1
RELAY
MODBUS
TT
TERMINALS
LINE
COMP 1
RELAY
COMP 2
RELAY
FOSSIL
FUEL
24 V
TYPICAL SYSTEM WIRING DIAGRAMS
ENTERING THE ADVANCED INSTALLER SETTINGS MENU
The T-32-P contains factory defaults for all Advanced Installer Settings. Depending upon the user
and equipment application, some settings may need to be changed.
To enter the Advanced Installer Settings menu, push the
button once, then hold it down (15
seconds) until the LCD displays
which is the first menu item. You can move forward or backwards
through the menu by pressing the
or
buttons.
O/RIDE
LC
O/RIDE
PROG
Symbol
Default
Function
LC
00
Keypad Lockout
Programmable Mode
LC=00 - All buttons are unlocked
LC=01 - All buttons are locked except ( ) ( ) buttons
LC=02 - All buttons are locked
LC
00
LC=00 - All buttons are unlocked
LC=02 - All buttons locked except ( ) ( ) buttons
LC=03 - PROG button is locked
LC=04 - All buttons are locked
ADVANCED INSTALLER SETTINGS MENU
(Sw6=ON)
(Sw6=OFF)
Non-programmable
Mode
9