13
Minimum Off Time
The minimum Off time prevents the compressor
from restarting too quickly. Large HVAC systems
should use a longer Off time. The minimum Off
time and the minimum Run time also influence the
cycling rate.
Press the
NEXT
key to select
Option 06
and
press the
Up
or
Down
key to set the Minimum
Off Time.
Option
CANCEL
NEXT
ENTER
14
Minimum Run Time
The Minimum Run Time influences the cycling
rate and helps to evaporate condensation in heat
ex-changers.
Press the
NEXT
key to select
Option 07
and
press the
Up
or
Down
key to set the Minimum
Run Time.
Option
CANCEL
NEXT
ENTER
15
Heating Setpoint Limit
The maximum heating setpoint the user can set
is 60 to 85F.
Press the
NEXT
key to select
Option 08
and
press the
Up
or
Down
key to set maximum
allowable heating setpoint.
Option
CANCEL
NEXT
ENTER
16
Cooling Setpoint Limit
The minimum cooling setpoint the user can set is
55 to 80F.
Press the
NEXT
key to select
Option 09
and
press the
Up
or
Down
key to set the minimum
allowable cooling setpoint.
Option
CANCEL
NEXT
ENTER
Set To
Set To
Set To
Set To
Set To
17
Heat / Cool Setpoint Differential
The Heat/Cool temperature differential
prevents the heating setpoint from being set
above or too close to the cooling setpoint,
resulting in inadvertent cycling between
heating and cooling.