background image

7

Press the 

NEXT

 key to select 

Option 11

 and 

press the 

Up

 or 

Down

 key to set the setpoint 

differential.

Option

CANCEL

NEXT

ENTER

Set To

First Stage Differential

First stage temperature differential determines the 
sensitivity of the thermostat.  A lower differential 
will cause the thermostat to cycle more often with 
smaller temperature swings. 
If the temperature differential between indoor 
temperature and setpoint temperature is greater 
than the first stage temperature differential, first 
stage heating or cooling will be activated.
Press the 

NEXT

 key to select 

Option 11

 and 

press the 

Up

 or 

Down

 key to set the first stage 

differential.

Option

CANCEL

NEXT

ENTER

18

Set To

19

Second Stage Differential

Second stage temperature differential 
determines when the equipment advances from 
first to second stage.  If the temperature 
differential between indoor temperature and 
setpoint exceeds the second stage temperature 
differential, the equipment activates second 
stage heating or cooling.

Press the 

NEXT 

key to select 

Option 12

 and the 

Up

 or 

Down

 key to set the second stage 

temperature differential.  If the first stage 
temperature differential is greater than third stage 
temperature differential, first stage differential will 
automatically be incremented.

Option

CANCEL

NEXT

ENTER

Set To

20

Third Stage Differential

Option

CANCEL

NEXT

ENTER

Set To

Third stage temperature differential determines 
when the equipment advances from second to 
third stage.  Setting the differential temperatures 
the same for second stage and third stage turns 
second and third stage on at the same time. 
Press the 

NEXT

 key to select 

Option 13 

and the 

Up

 or 

Down

 key to set the third stage 

temperature differential. The third stage 
temperature differential cannot be set below the 
second stage differential.

Stage Timing

The Staging Override Time will turn on the next 
stage even though the temperature differential has 
not been reached.

Press the 

NEXT

 key to select 

Option 14 

and the 

Up

 or 

Down

 key to set the stage timing.

21

Summary of Contents for WCT-32

Page 1: ...f a communications interruption Wireless 915MHz proprietary protocol with up to 100 transmission range Easy access front loading battery compartment 2 AA batteries included Application Features Compatible Equipment Output Terminals Fan Operation LED Indicator Communications Range Control Module Power Control Module Housing Control Module Dimensions Thermostat Dimensions Single stage multi stage an...

Page 2: ...ws are included or the module can be installed with double backed adhesive tape 1 COM COM Gas Electric HVAC System Heat Pump System R R Y1 Y1 Y2 Y2 W2 W2 E O W1 B G G Wiring Heat Pump up to 3 heat 2 cool The HVAC module is powered by the 24VAC from HVAC system The diagrams below show wiring when configured for Gas Electric and Heat Pump systems 2 W1 B W1 B O O W2 E W2 E Y1 Y1 Y2 Y2 G G R R C C 2 6...

Page 3: ...ll Avoid placing the thermsotat in areas where the air movement is limited affected by direct sunlight or other areas not typical of the temperature in the space Location 3 The thermostat should be installed approximately 5 feet above the floor Level the sub base for appearance and use the wall anchors and screws provided Installing the Sub Base 5 Slide the battery cover off and install two AA bat...

Page 4: ...R key if no more options are to be changed Option Zone CANCEL NEXT ENTER Setting the Zone Number Press the NEXT key to select Option 02 The Home number is used to distinguish between thermostats and HVAC Control Modules that are less than 500 feet away from one another This could be a home with two HVAC systems or a multi family residence Setting the Home number The installer options can be access...

Page 5: ...d press the Up or Down key to select 00 Gas Electric or 01 Heat Pump operation 11 Set To Fan Operation Press the NEXT key to select Option 05 The fan can be set to 00 Gas operation where the equipment activates the HVAC system fan during heating calls or to 01 Electric operation where the module activates the fan during heating calls In heat pumps and all cooling calls the module activates the fan...

Page 6: ...key to set the Minimum Run Time Option CANCEL NEXT ENTER 15 Heating Setpoint Limit The maximum heating setpoint the user can set is 60 to 85F Press the NEXT key to select Option 08 and press the Up or Down key to set maximum allowable heating setpoint Option CANCEL NEXT ENTER 16 Cooling Setpoint Limit The minimum cooling setpoint the user can set is 55 to 80F Press the NEXT key to select Option 09...

Page 7: ...stage temperature differential the equipment activates second stage heating or cooling Press the NEXT key to select Option 12 and the Up or Down key to set the second stage temperature differential If the first stage temperature differential is greater than third stage temperature differential first stage differential will automatically be incremented Option CANCEL NEXT ENTER Set To 20 Third Stage...

Page 8: ...e supplied User Manual Although great care has been taken in preparation of this manual Specified Controls takes no responsibility for errors or omissions contained herein It is the responsibility of the installer to ensure that this thermostat and the equipment connected to it operate in a safe and efficient manner Due to ongoing product improvements Specified Controls reserves the right to chang...

Reviews: