The WZ1-T is a battery powered, auto-changeover thermostat
that communicates via an RF wireless data link to a damper
control module located on the Zone One™ damper. The
system is designed to prevent overheating and overcooling of
individual zones.

.

An automatic changeover duct sensor located on the damper
senses whether there is warm air or cool air in the branch
supply duct. If the Zone One™ thermostat is calling for cooling
and the duct sensor determines there is cool air in the duct, the
damper will power open; otherwise, the damper will remain
closed. If the Zone One™ thermostat is calling for heating and
the duct sensor determines there is warm air in the duct, the
damper will power open; otherwise, the damper will remain
closed. The relay control module has LED indication to confirm
mode of operation and damper position.

Up to 8 WZ1 thermostat controlled dampers

can be used in the same location

Application

Damper Actuator Type

Communications Indicator

Damper Position Indicator

Communications

Range

Control Module Power

Control Module Housing

Control Module Dimensions

Thermostat Dimensions

24 Volt, 10 VA, 2-wire, powered open / spring return close

Multi-color LED indicates mode of operation

Green LED indicates when damper is open

Wireless, 915MHz, proprietary protocol

Up to 100 feet

24VAC, 40VA

Molded plastic

3.25 x 5.50 x 1.125 inches (WHD)

5.00 x 4.50 x 1.00 inches (WHD)

Wireless

ZONE NE

TM

Made in the USA

Specifications

Sequence of operation

SYSTEM

FAN

Model WZ1

Summary of Contents for WZ1

Page 1: ...ensor determines there is warm air in the duct the damper will power open otherwise the damper will remain closed The relay control module has LED indication to confirm mode of operation and damper po...

Page 2: ...rmostat should be located in the area being controlled by the zone damper and away from the HVAC unit thermostat Do not install the thermostat in an area where drafts are present near the floor behind...

Page 3: ...thermostat should be installed approximately 5 feet above the floor Level the subbase for appearance and use the wall anchors and screws provided Installing the Subbase 4 Slide the battery cover off...

Page 4: ...n seconds The LCD displays Option 01 for setting the number See Installer Options Chart Press or hold the key to advance to the next option The LCD will advance through to Option 09 and then return to...

Page 5: ...r normally flashes green when no calls are active The LED is continuously yellow during cooling calls and red during heating calls 9 Cooling Setpoint Limit Press the key to select and press the or key...

Page 6: ...EM key selects Auto and Off Fan key Not used Temperature Setting Space temperature Menu key used to set time of day and day of week Cancel key used to cancel changes Next key used when setting time of...

Page 7: ...the and keys to set the hour Make sure that the AM or PM is correct MENU Up Down Press the key to set the minute Use the and keys to set the minute Press the key to set the current day of the week Us...

Page 8: ...f the Wireless Zone One system and its components without notice All rights reserved Jackson Systems LLC 2010 Intellectual rights apply To reset the factory defaults remove the batteries and re instal...

Reviews: