Installation and Operation Manual
The WZ1-T is a battery powered, auto-changeover thermostat
that communicates via an RF wireless data link to a damper
control module located on the Zone One™ damper. The
system is designed to prevent overheating and overcooling of
individual zones.
.
An automatic changeover duct sensor located on the damper
senses whether there is warm air or cool air in the branch
supply duct. If the Zone One™ thermostat is calling for cooling
and the duct sensor determines there is cool air in the duct, the
damper will power open; otherwise, the damper will remain
closed. If the Zone One™ thermostat is calling for heating and
the duct sensor determines there is warm air in the duct, the
damper will power open; otherwise, the damper will remain
closed. The relay control module has LED indication to confirm
mode of operation and damper position.
Up to 8 WZ1 thermostat controlled dampers
can be used in the same location
Application
Damper Actuator Type
Communications Indicator
Damper Position Indicator
Communications
Range
Control Module Power
Control Module Housing
Control Module Dimensions
Thermostat Dimensions
24 Volt, 10 VA, 2-wire, powered open / spring return close
Multi-color LED indicates mode of operation
Green LED indicates when damper is open
Wireless, 915MHz, proprietary protocol
Up to 100 feet
24VAC, 40VA
Molded plastic
3.25 x 5.50 x 1.125 inches (WHD)
5.00 x 4.50 x 1.00 inches (WHD)
Wireless
ZONE NE
TM
Made in the USA
Specifications
Sequence of operation
SYSTEM
FAN
Model WZ1