-102-
normal.
P9.67
Over-speed detection value
0.0%~50.0%( maximum frequency)
20.0%
☆
P9.68
Over-speed detection time
0.0s~60.0s
1.0s
☆
This function is valid only when the Inverter runs in the FVC mode.
If the actual motor rotational speed detected by the Inverter exceeds the maximum
frequency and the excessive value is greater than the value of P9.67 and the lasting time
exceeds the value of P9.68, the Inverter reports 43=E.oSF and acts according to the selected
fault protection action.
If the over-speed detection time is 0.0s, the over-speed detection function is disabled.
P9.69
Detection value of too large
speed deviation
0.0%~50.0%( maximum frequency)
20.0%
☆
P9.70
Detection time of too large
speed deviation
0.0s~60.0s
5.0s
☆
This function is valid only when the Inverter runs in the FVC mode.
If the Inverter detects the deviation between the actual motor rotational speed detected by
the Inverter and the set frequency is greater than the value of P9.69 and the lasting time exceeds
the value of P9.70, the Inverter reports 42=E.Sdl and according to the selected fault protection
action.
If P9.70 (Detection time of too large speed deviation) is 0.0s, this function is disabled.
Summary of Contents for DLB1-0D40S2G
Page 11: ...11 Graph 1 722 30KW product outline dimensions Graph 1 837 55KW product outline dimensions...
Page 12: ...12 Graph 1 875 110KW product outline dimensions Graph 1 9 132 160KW product outline dimensions...
Page 14: ...14 2 Wirings 2 1 Standard wiring diagrams Graph 2 8 0 4 18 5KW inverter wiring diagram...
Page 15: ...15 Graph 2 922 400KW inverter wiring diagram...
Page 159: ...159...