-135-
ADR
01H
CMD
03H
Byte number high place
00H
Byte number low place
04H
F002H high place
00H
F002H low place
00H
F003H high place
00H
F003H high place
01H
CRC CHK low place
CRC CHK value
CRC CHK high place
Command code:06H write one word
For example:write 5000(1388H) toF00AH of slave address02H.
Master command information
ADR
02H
CMD
06H
Information address high place
F0H
Informationaddress low place
0AH
Information content high place
13H
Information content low place
88H
CRC CHK low place
CRC CHK value
CRC CHK high place
Slave response information
ADR
02H
CMD
06H
Informationaddress high place
F0H
Informationaddress low place
0AH
Information content high place
13H
Information content low place
88H
CRC CHK low place
CRC CHK value
CRC CHK high place