2.3 Control circuit wiring terminals
2.3.1 Control circuit terminal definitions
GND
AO1
AO2
AI1
AI2
AI3
DI2
DI4
DI6
DO1
COM
TC1
GND
+10V
+24V
SP
COM
DI1
DI3
DI5
FM
+24V
TA1
TB1
2.3.2 Control circuit signals
Category
Terminal
Name
Function
Specifications
Input
D
igital
DI1
Multi-function
input terminal
X1
Default setting: Forward
operation(FWD)
Optical coupler
insulation
DC24V/8mA
When using external
power supply,
voltage range: 9
~
30V
DI5 can configure as
high speed pulse
input. pulse range:
0
~
100kHz.
DI2
Multi-function
input terminal
X2
Default setting: Forward
JOG(FJOG)
DI3
Multi-function
input terminal
X3
Default setting: Fault reset
(RESET)
DI4
Multi-function
input terminal
X4
Default setting: Multi-speed
terminal1
DI5
Multi-function
input terminal
X5
Default setting: Multi-speed
terminal12
DI6
Multi-function
input terminal
X6
Default setting: REV
operation(REV)
SP
Multi-function
input common
Default: +24V short-circuit with SP
by jumper
Analog
10V
Analog
10V
Power
Output capacity: 10mA or below,
1kΩ~5kΩ
0
~
20mA input: input
impedance is 500
ohms.
0
~
10V input: input
impedance is 20K
ohms.
AI1
Analog
frequency setting
1
DC: 0
~
10V or 0
~
20mA
(resolution1/1000)
AI2
Analog
frequency setting
2
DC: 0
~
10V or 0
~
20mA
(resolution1/1000)
AGND
Analog common
0V
Summary of Contents for DLB1-0D40S2G
Page 11: ...11 Graph 1 722 30KW product outline dimensions Graph 1 837 55KW product outline dimensions...
Page 12: ...12 Graph 1 875 110KW product outline dimensions Graph 1 9 132 160KW product outline dimensions...
Page 14: ...14 2 Wirings 2 1 Standard wiring diagrams Graph 2 8 0 4 18 5KW inverter wiring diagram...
Page 15: ...15 Graph 2 922 400KW inverter wiring diagram...
Page 159: ...159...