-18-
Category
Terminal
Name
Function
Specifications
terminal
Out
p
u
t
R
elay
TA1
A node output
Default setting: stop fault during
operation
TA1—TC1: normally open
TB1—TC1: normally close
Node capacity:
AC250V, 3A.
TB1
B node output
TZ1
Node output
common terminal
D
igital
DO1
Open collector
output
1
Default setting: inverter in
operation
open collector output;
Optical-coupler
output capacity:
Below DC24V, 50mA.
FM
High speed pulse
output
Pulse range: 0
~
100kHz.
Open collector output.
Defined by P5.00: FM
terminal output mode
selection.
When used as high
speed pulse output,
maximum frequency
is 100kHz.
COM
FM output
common terminal
Analog
AO1
Analog monitor
output1
Voltage or current output;
Default setting:output frequency
Output voltage range:
0
~
10V;
Output current range:
0
~
20mA.
AO2
Analogm monitor
output2
Voltage or current output;
Default setting: output frequency
AGND
Analog common
terminal
0V
Power
+24V
DC24V power
positive node
Used with DI, DO
Output
capacity:below
200mA;
Default:
+24V short-circuit
with SP
COM
DC24V power
negative node
Summary of Contents for DLB1-0D40S2G
Page 11: ...11 Graph 1 722 30KW product outline dimensions Graph 1 837 55KW product outline dimensions...
Page 12: ...12 Graph 1 875 110KW product outline dimensions Graph 1 9 132 160KW product outline dimensions...
Page 14: ...14 2 Wirings 2 1 Standard wiring diagrams Graph 2 8 0 4 18 5KW inverter wiring diagram...
Page 15: ...15 Graph 2 922 400KW inverter wiring diagram...
Page 159: ...159...