-41-
4.3 First motor parameters:P1.00-P1.37
Code
Description
Setting range
Defa
ult
Restricti
ons
P1.00
Motor type selection
Common asynchronous motor
0
0
★
Variable frequency asynchronous
motor
1
Permanent magnetic synchronous
motor
2
P1.01
Motorrated power
0.1kW~1000.0kW
-
★
P1.02
Motorrated voltage
1V~2000V
-
★
P1.03
Motorrated current
0.01A~655.35A( inverter rated
power
≦
55kW )
0.1A~6553.5A( inverter rated
power >55kW)
-
★
P1.04
Motorrated frequency
0.01Hz~ maximum frequency
-
★
P1.05
Motorrated speed
1rpm~65535rpm
-
★
Set the parameters according to the motor nameplate no matter whether V/F control or vector
control is adopted.
To achieve better V/F or vector control performance, motor auto-tuning is required. The motor
auto-tuning accuracy depends on the correct setting of motor nameplate parameters.
P1.06
Asynchronous motor stator
resistance
0.001Ω~65.535Ω( inverter power<=55kW)
0.0001Ω~6.5535Ω( inverter power>55kW)
-
★
P1.07
Asynchronous motor
rotorresistance
0.001Ω~65.535Ω( inverter power<=55kW)
0.0001Ω~6.5535Ω( inverter power>55kW)
-
★
P1.08
Asynchronous motor
leakage inductive reactance
0.01mH~655.35mH( inverter
power<=55kW)
0.001mH~65.535mH( inverter
power>55kW)
-
★
P1.09
Asynchronous motor mutual
inductive reactance
0.1mH~6553.5mH( inverter
power<=55kW)
0.01mH~655.35mH( inverter
power>55kW)
-
★
P1.10
Asynchronous motor no
load current
0.01A~P1.03( inverter power<=55kW)
0.1A~P1.03( inverter power>55kW)
-
★
The parameters in P1.06 to P1.10 are asynchronous motor parameters. These parameters are
unavailable on the motor nameplate and are obtained by motor auto-tuning. Only P1.06 to P1.08 can be
obtained through static motor auto-tuning. Through complete motor auto-tuning, encoder phase
sequence and current loop PI can be obtained besides the parameters in P1.06 to P1.10.
Each time "Motor rated power" (P1.01) or “Motor rated voltage" (P1.02) is changed, the Inverter
automatically restores values of P1.06 to P1.10 to the parameter setting for the common standard Y
series asynchronous motor.
If it is impossible to perform motor auto-tuning onsite, manually input the values of these
parameters according to data provided by the motor manufacturer.
Summary of Contents for DLB1-0D40S2G
Page 11: ...11 Graph 1 722 30KW product outline dimensions Graph 1 837 55KW product outline dimensions...
Page 12: ...12 Graph 1 875 110KW product outline dimensions Graph 1 9 132 160KW product outline dimensions...
Page 14: ...14 2 Wirings 2 1 Standard wiring diagrams Graph 2 8 0 4 18 5KW inverter wiring diagram...
Page 15: ...15 Graph 2 922 400KW inverter wiring diagram...
Page 159: ...159...