-45-
Before performing no-load auto-tuning, properly set the motor type, motor nameplate parameters of
P1.00 to P1.05, "Encoder type" (P1.28) and "Encoder pulses per revolution" (P1.27) and "Number of
pole pairs of resolver" (P1.34) first.
The Inverter will obtain motor parameters of P1.16 to P1.20, encoder related parameters of P1.30
to P1.33 and vector control current loop PI parameters of P3.13 to P3.16 by no-load auto-tuning.
Set this parameter to 12, and press RUN. Then, the Inverter starts no-load auto-tuning.
Motor auto-tuning can be performed only in operation panel mode.