-58-
47
Emergency stop
When this terminal becomes ON, the Inverter stops within
the shortest time. During the stop process, the current
remains at the set current upper limit. This function is used
to satisfy the requirement of stopping the Inverter in
emergency state.
48
External STOP
terminal 2
In any control mode (operation panel, terminal or
communication), it can be used to make the Inverter
decelerate to stop. In this case, the deceleration time is
deceleration time 4.
49
Deceleration DC
braking
When this terminal becomes ON, the Inverter decelerates to
the initial frequency of stop DC braking and then switches
over to DC braking state.
50
Clear the current
running time
When this terminal becomes ON, the Inverter's current
running time is cleared. This function must be supported by
P8.42 and P8.53.
51~59
Reserved
Reserved
The four multi-reference terminals have 16 state combinations, corresponding to 16 reference
values, as listed in the following table.
K4
K3
K2
K1
Reference
setting
Corresponding
parameter
OFF
OFF
OFF
OFF
Reference 0
PC.00
OFF
OFF
OFF
ON
Reference 1
PC.01
OFF
OFF
ON
OFF
Reference 2
PC.02
OFF
OFF
ON
ON
Reference 3
PC.03
OFF
ON
OFF
OFF
Reference 4
PC.04
OFF
ON
OFF
ON
Reference 5
PC.05
OFF
ON
ON
OFF
Reference 6
PC.06
OFF
ON
ON
ON
Reference 7
PC.07
ON
OFF
OFF
OFF
Reference 8
PC.08
ON
OFF
OFF
ON
Reference 9
PC.09
ON
OFF
ON
OFF
Reference 10
PC.10
ON
OFF
ON
ON
Reference 11
PC.11
ON
ON
OFF
OFF
Reference 12
PC.12
ON
ON
OFF
ON
Reference 13
PC.13
ON
ON
ON
OFF
Reference 14
PC.14
ON
ON
ON
ON
Reference 15
PC.15
If the frequency source is multi-reference, the value 100% of FC-00 to FC-15 corresponds to the
value of P0.10 (Maximum frequency).
Besides the multi-speed function, the multi-reference can be also used as the PID setting source or
the voltage source for V/F separation, satisfying the requirement on switchover of different setting values.
Summary of Contents for DLB1-0D40S2G
Page 11: ...11 Graph 1 722 30KW product outline dimensions Graph 1 837 55KW product outline dimensions...
Page 12: ...12 Graph 1 875 110KW product outline dimensions Graph 1 9 132 160KW product outline dimensions...
Page 14: ...14 2 Wirings 2 1 Standard wiring diagrams Graph 2 8 0 4 18 5KW inverter wiring diagram...
Page 15: ...15 Graph 2 922 400KW inverter wiring diagram...
Page 159: ...159...