-67-
High level valid
0
Low level valid
1
Hundred’s place
DI3 valid mode
High level valid
0
Low level valid
1
Thousand's place
DI4 valid mode
High level valid
0
Low level valid
1
Ten Thousand's
place
DI5 valid mode
High level valid
0
Low level valid
1
P4.39
DI mode
selection2
One’s place
DI6 valid mode
00000
★
High level valid
0
Low level valid
1
Ten’s place
DI7 valid mode
High level valid
0
Low level valid
1
Hundred’s place
DI8 valid mode
High level valid
0
Low level valid
1
Thousand's place
DI9 valid mode
High level valid
0
Low level valid
1
Ten Thousand's
place
DI10 valid mode
High level valid
0
Low level valid
1
These parameters are used to set the valid mode of DI terminals.
•
0: High level valid
The DI terminal is valid when being connected with COM, and invalid when being disconnected from
COM.
•
1: Low level valid
The DI terminal is invalid when being connected with COM, and invalid when being disconnected
from COM.