-71-
35
Module temperature reached
If the heatsink temperature of the inverter
module (P7.07) reaches the set module
temperature threshold (P8.47), the terminal
becomes ON.
36
Software current limit
exceeded
Refer to the descriptions of P8.36 and
P8.37.
37
Frequency lower limit
reached (having output at
stop)
If the running frequency reaches the lower
limit, the terminal becomes ON. In the stop
state, the signal is still ON.
38
Alarm output
If a fault occurs on the Inverter and the
Inverter continues to run, the terminal
outputs the alarm signal.
39
Motor overheat warning
If the motor temperature reaches the
temperature set in P9.58 (Motor overheat
warning threshold), the terminal becomes
ON. You can view the motor temperature
by using d0.34.
40
Current running time reached
If the current running time of Inverter
exceeds the value of P8.53, the terminal
becomes ON.
42
Command status
Direct output
43
FWD command status
44
REV command status
P5.06
FMP output selection
0-16
0
☆
P5.07
AO1 output selection
0-16
0
☆
P5.08
AO2 output selection
0-16
1
☆
The output pulse frequency of the FMP terminal ranges from 0.01 kHz to "Maximum FMP output
frequency" (P5.09). The value of P5.09 is between 0.01 kHz and 100.00 kHz.
The output range of AO1 and AO2 is 0-10 V or 0-20 mA. The relationship between pulse and
analog output ranges and corresponding functions is listed in the following table.
Value
Function
Description
0
Running frequency
0 to maximum output frequency
1
Set frequency
0 to maximum output frequency
2
Output current
0 to 2 times of rated motor current
3
Output torque (absolute value)
0 to 2 times of rated motor torque
4
Output power
0 to 2 times of rated power
Summary of Contents for DLB1-0D40S2G
Page 11: ...11 Graph 1 722 30KW product outline dimensions Graph 1 837 55KW product outline dimensions...
Page 12: ...12 Graph 1 875 110KW product outline dimensions Graph 1 9 132 160KW product outline dimensions...
Page 14: ...14 2 Wirings 2 1 Standard wiring diagrams Graph 2 8 0 4 18 5KW inverter wiring diagram...
Page 15: ...15 Graph 2 922 400KW inverter wiring diagram...
Page 159: ...159...