-83-
P8.12
Forward/Reverse rotation
dead-zone time
0.00s~3000.0s
0.0s
☆
It is used to set the time when the output is 0 Hz at transition of the Inverter forward rotation and
reverse rotation, as shown in the following figure.
P8.13
Reverse control
Enabled
0
0
☆
Disabled
1
It is used to set whether the Inverter allows reverse rotation. In the applications where reverse
rotation is prohibited, set this parameter to 1.
P8.14
Running mode when set
frequency lower than
frequency lower limit
Run at frequency lower limit
0
0
☆
Stop (needs startcommand)
1
Run at zero speed
2
Stop (restart automatically if
frequency is higher than lower limit)
3
time
t
Output
Frequency
Hz
FWD
REV
dead-zone time