P8.25
Frequency switchover point
between acceleration time 1
and acceleration time 2
0.00Hz~ maximum frequency
0.00Hz
☆
P8.26
Frequency switchover point
between deceleration time 1
and deceleration time 2
0.00Hz~ maximum frequency
0.00Hz
☆
This function is valid when motor 1 is selected and acceleration/deceleration time switchover is
not performed by means of DI terminal. It is used to select different groups of acceleration/
deceleration time based on the running frequency range rather than DI terminal during the running
process of the Inverter.
During acceleration, if the running frequency is smaller than the value of P8.25, acceleration time
2 is selected. If the running frequency is larger than the value of P8.25, acceleration time 1 is selected.
During deceleration, if the running frequency is larger than the value of P8.26, deceleration time 1
is selected. If the running frequency is smaller than the value of P8.26, deceleration time 2 is selected.