P8.27
Terminal JOG preferred
Disabled
0
0
☆
Enabled
1
It is used to set whether terminal JOG is preferred.
If terminal JOG is preferred, the Inverter switches to terminal JOG running state when there is a
terminal JOG command during the running process of the Inverter.
P8.28
Frequency detection value
(FDT2)
0.00Hz~ maximum frequency
50.00Hz
☆
P8.29
Frequency detection
hysteresis (FDT hysteresis
2)
0.0%~100.0%(FDT2 Level)
5.0%
☆
The frequency detection function is the same as FDT1 function. For details, refer to the
descriptions of P8.19 and P8.20.
P8.30
Any frequency reaching
detection value 1
0.00Hz~ maximum frequency
50.00Hz
☆
P8.31
Any frequency reaching
detection amplitude 1
0.0%~100.0%( maximum frequency)
0.0%
☆
P8.32
Any frequency reaching
detection value 2
0.00Hz~ maximum frequency
50.00Hz
☆
P8.33
Any frequency reaching
detection amplitude 2
0.0%~100.0%( maximum frequency)
0.0%
☆
If the output frequency of the Inverter is within the positive and negative amplitudes of the any
frequency reaching detection value, the corresponding DO becomes ON.
The DLB1 provides two groups of any frequency reaching detection parameters, including
frequency detection value and detection amplitude, as shown in the graph above.
P8.34
Zero current detection level
0.0%~300.0%( motorrated current)
5.0%
☆
P8.35
Zero current detection delay
time
0.00s~600.00s
0.10s
☆
If the output current of the Inverter is equal to or less than the zero current detection level and the
duration exceeds the zero current detection delay time, the corresponding DO becomes ON. The zero
current detection is shown in the following figure.
Running frequency
time t
Any frequency
reaching detection
value
Any Frequency
detection value
DO or relay
ON
ON
OFF
OFF
OFF
Any frequency reaching detection amplitude
Any frequency reaching detection amplitude
Summary of Contents for DLB1-0D40S2G
Page 11: ...11 Graph 1 722 30KW product outline dimensions Graph 1 837 55KW product outline dimensions...
Page 12: ...12 Graph 1 875 110KW product outline dimensions Graph 1 9 132 160KW product outline dimensions...
Page 14: ...14 2 Wirings 2 1 Standard wiring diagrams Graph 2 8 0 4 18 5KW inverter wiring diagram...
Page 15: ...15 Graph 2 922 400KW inverter wiring diagram...
Page 159: ...159...