-90-
P8.38
Any current reaching 1
0.0%~300.0%( motorrated current)
100.0%
☆
P8.39
Any current reaching
amplitude 1
0.0%~300.0%( motorrated current)
0.0%
☆
P8.40
Any current reaching 2
0.0%~300.0%( motorrated current)
100.0%
☆
P8.41
Any current reaching
amplitude 2
0.0%~300.0%( motorrated current)
0.0%
☆
If the output current of the Inverter is within the positive and negative amplitudes of any current
reaching detection value, the corresponding DO becomes ON.
The DLB1 provides two groups of any current reaching detection parameters, including current
detection value and detection amplitudes, as shown in the following figure
P8.42
Timing function
Disabled
0
0
☆
Enabled
1
P8.43
Timing duration source
P8.44 setting
0
0
☆
AI1
1
AI2
2
AI3( keyboard potentiometer)
3
P8.44
Timing duration
0.0Min~6500.0Min
0.0Min
☆
If P8.42 is set to 1, the Inverter starts to time at startup. When the set timing duration is reached,
the Inverter stops automatically and meanwhile the corresponding DO becomes ON.
The Inverter starts timing from 0 each time it starts up and the remaining timing duration can be
queried by d0.20.
The timing duration is set in P8.43 and P8.44, in unit of minute.
P8.45
AI1 input voltage lower limit
0.00V~P8.46
3.10V
☆
P8.46
AI1 input voltage upper limit
P8.45~10.00V
6.80V
☆
These two parameters are used to set the limits of the input voltage to provide protection on the
Inverter. When the AI1 input is larger than the value of P8.46 or smaller than the value of P8.45, the
corresponding DO becomes ON, indicating that AI1 input exceeds the limit.
ON
ON
ON
OFF
OFF
OFF
Any current reaching amplitude
Any current reaching amplitude
Any current detection
DO
or relay
Output
current
time t
Any current
reaching
Summary of Contents for DLB1-0D40S2G
Page 11: ...11 Graph 1 722 30KW product outline dimensions Graph 1 837 55KW product outline dimensions...
Page 12: ...12 Graph 1 875 110KW product outline dimensions Graph 1 9 132 160KW product outline dimensions...
Page 14: ...14 2 Wirings 2 1 Standard wiring diagrams Graph 2 8 0 4 18 5KW inverter wiring diagram...
Page 15: ...15 Graph 2 922 400KW inverter wiring diagram...
Page 159: ...159...