-98-
P9.48
Fault protection action
selection 2
One’s
place
Encoder fault (20=E.PG1)
000
00
☆
Coast to stop
0
Switch to V/F mode and stop according
to stop mode
1
Switch to V/F mode and continue to run
2
Ten’s
place
EEPROM fault (21=E.EEP)
Coast to stop
0
Stop according to stop mode
1
Hundr
ed’s
place
reserved
Thous
and's
place
Motor overheat (45= E.oHt)
Coast to stop
0
Stop according to stop mode
1
Continue to run
2
Ten
thous
and's
place
Accumulative running time
reached (26= E.ArA)
Coast to stop
0
Stop according to stop mode
1
Continue to run
2
P9.49
Fault protection action
selection 3
One’s
place
User defined fault 1 (27=
E.USt1)
000
00
☆
Coast to stop
0
Stop according to stop mode
1
Continue to run
2
Ten’s
place
User defined fault 2(28= E.USt2)
Coast to stop
0
Stop according to stop mode
1
Continue to run
2
Hundr
ed’s
place
Accumulative power-on time
reached (29= E.APA)