Connect the device to the hydraulic system by using the specified inlet/ outlet connections. Make sure that the connections are
air tight, use a sealant for this. The coil is equipped with a de-aerater.
If the unit is used for cooling, the hydraulic pipes must be insulated.
When using devices for cooling: iron couplings prohibited.
05
Use a back-off wrench when fastening the
hydronic connections !
Remove black plug at hydraulic
connection.
IN
OUT
Install the condensate drain. The device must be hung with a downward slant towards the condensate drain, to ensure that the
condensation water is drained quickly. (3cm/m)
The condensate drain system must be set up with an adequate p-trap in order to prevent the infiltration of odours. Always install
a plug for cleaning in the lower part of the p-trap in order to allow quick disassembly.Pour water into the condensate collection
pan and check if the liquid is drained properly. Otherwise, check the inclination and look for possible blockages.
If the condensation drain pan is not used, the drain pipe must be connected directly to the condensation trap. In this
case, the hydraulic pipes and the valves used for cooling water must be insulated against condensation
Position the drain pipes without mechanical stress on the drain connection of the unit.
06
EN
13