5.3. OPERATING LIMITS
If the appliance is supplied with chilled water, the condensation forming on the heat exchanger will
be drained via the condensation drain connection.
At very low chilled water temperature and very high humidity, condensation may form on compo-
nents other than the heat exchanger. This is not collected in the condensation drain, but might drip
from under the appliance.
To avoid this, a minimum permitted water temperature must be taken into account in function of the
relative humidity and temperature of the ambient air.
5.3.1. PERMITTED MINIMUM WATER TEMPERATURE (°C)
AMBIENT TEMPERATURE / DRY BULB TEMPERATURE (°F)
69.8 °F
73.4 °F
77 °F
80.6 °F
84.2 °F
87.8 °C
RH (%)
40 %
37.4
°F
37.4
°F
37.4
°F
37.4
°F
37.4
°F
39.2
°F
50 %
37.4
°F
37.4
°F
37.4
°F
37.4
°F
39.2
°F
42.8
°F
60 %
37.4
°F
37.4
°F
39.2
°F
39.2
°F
42.8
°F
46.4
°F
70 %
37.4
°F
39.2
°F
41
°F
42.8
°F
46.4
°F
50
°F
80 %
39.2
°F
41
°F
42.8
°F
46.4
°F
50
°F
/
90 %
41
°F
42.8
°F
46.4
°F
50
°F
/
/
100 %
42.8
°F
46.4
°F
50
°F
/
/
/
Permitted minimum water temperature
EN
7
JAGA CANADA | BRIZA 26 | MANUEL | 2022.09.27 | V.01