58
JAGA NV | BRIZA RAD 055/041 | MANUAL | 5 JULI 2021, 14:29 | V.01
A. MANUALLY WITH WATER TEMPERATURE MONITORING
Configuration code : DPC.BR21 / DPC.BR22 / DPC.BR24 / DPC.BR25
24 V +
GND
1
2P
MODE
[2]
Only DPC.BR24 /
DPC.BR25
A.1. FACTORY SETTINGS
A.1.1. Without control panel
Configuration code : DPC.BR21 / DPC.BR22
The unit is controlled by the water temperature The unit starts as soon as the set water temperature
has been reached.
The unit starts as soon as the water temperature > 28 ̊C.
Only with configuration code DPC.BR22! The unit starts as soon as the water temperature < 18 ̊C.
1 Speed . The unit runs at the set speed.
A.1.2. With control pannel
Configuration code : DPC.BR24 / DPC.BR25
The user manually selects the desired mode via the control panel (
/
/
Off
). The unit can run at
3 speeds. The unit starts as soon as the set water temperature has been reached.
The unit starts at the last selected speed(1, 2 or 3), as soon as the water temperature > 28 ̊C.
Only with configuration code DPC.BR25! The unit starts at the last selected speed(1, 2 or 3), as
soon as the water temperature < 18 ̊C.
Off
All functions are disabled until the user switches on the unit via the control panel.
-
-
3 speeds . The unit can run at 3 speeds.