5
1
Adjusting Fan speed
SPEED %:
20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
I
-
+
I
(MIN) The blue LED blinks fast
The red LED blinks fast (MAX)
Adjusting the Fan speed:
• short press “-” or “+” to adjust the speed of the
motor(s).
• after the adjustment of the speed, the fans will run
for 30” in order to control, irrespective of the water
temperature. The water-temperature sensor will
not respond during this time (position 2, 4, 6 or 7).
Any modification will be automatically stored in the
internal (EE PROM) memory.
-
+
-
+
MODE
0
F
E
DC
B A 9 8 7 6
5 4
32
1
Clima Canal JDPC.002
Dynamic Product Controller: Table 1 / 2 / 3
Setting the water temperature
2
Setting the minimum water temperature
heating
(default =>28 ° C)
A
Setting temperature ° C
24°C
26°C
28°C
30°C
32°C
34°C
36°C
38°C
I
- 2°C
+ 2°C
I
Press and hold the (+) button until the
red LED
flashes 5 times.
-
+
MODE
0
F
E
DC
B A 9 8 7 6
5 4
32
1
B
Increasing temperature
Briefly press (+): the temperature increases by one step 2 ° C.
If the
maximum temperature
is reached, the
red LED
flashes
rapidly.
Decrease temperature
Briefly press (-): the temperature decreases by one step 2 ° C.
If the
minimum temperature
is reached, the
blue LED
will flash
rapidly. After 30”, the JDPC module returns to normal mode.
Automatic control:
The
green LED
lights when the water temperature exceeds the set
temperature. This indicates that the supply water is hot.
Each adjustment is stored in the internal (EE PROM) memory.
C
Exit setup mode by holding the “+” button
until the
red LED
blinks 5x.
-
+
MODE
0
F
E
DC
B A 9 8 7 6
5 4
32
1
3
Setting the maximum temperature
of cooling water
(default = <18°C)
A
Setting temperature ° C
12°C
14°C
16°C
18°C
20°C
22°C
24°C
26°C
I
- 2°C
+ 2°C
I
Press and hold the (+) button until the
blue LED
flashes 5 times.
-
+
MODE
0
F
E
DC
B A 9 8 7 6
5 4
32
1
B
Increasing temperature
Briefly press (+): the temperature increases by one step 2 ° C.
If the maximum temperature is reached, the
red LED
flashes
rapidly.
Decrease temperature
Briefly press (-): the temperature decreases by one step 2 ° C.
If the minimum temperature is reached, the
blue LED
will flash
rapidly. After 30”, the JDPC module returns to normal mode.
Automatic control:
The
green LED
lights when the water temperature is lower than the
set temperature. This indicates that the supply water temperature
is colder.
Each adjustment is stored in the internal (EE PROM) memory.
C
Exit setup mode by holding the “+” button
until the
blue LED
blinks 5x.
-
+
MODE
0
F
E
DC
B A 9 8 7 6
5 4
32
1
!!
The JDPC controller returns into normal mode after 30” and will automatically save all modified settings
!!
5x
5x
5x
5x
default factory temperature setting
Summary of Contents for Clima Canal JDPC.002
Page 7: ...7 Notes...