MANUAL for JAKKA ADVANCED CONTROLLER

Note  2:  If  Supply  Air  Temperature  Sensor  is connected and 
necessary settings are made, Supply Air Temperature value 
is displayed in the panel at regular intervals. It has no cont-
rol function. 
Note 3: If Outdoor Air Temperature Sensor is connected and 
necessary  settings are  made,  Outdoor  Air  Temperature  va-
lue is displayed in the panel at regular intervals. 
Electrical heater can be controlled by the Outdoor Air Tem-
perature.  Electrical  Heater  control  is  performed  by  the  Re-
turn Air Temperature sensor value by default. 

Supply Air Temperature 

Room Temperature 

5. FAN SPEED SETTINGS

Fan speed can be set to one of 1-2-3-4-5-Auto values. 

Supply Air Fan Speed Setting : 
When pressing the FAN key once, Supply Air Fan icon 

flashes on the panel. While icon flashing, fan 

speed can be changed by 

▲ and ▼

 key. 

Exhaust Air Fan Speed Setting : 
When pressing the FAN key twice, Exhaust Air Fan 

icon 

flashes on the panel. While icon flashing, 

fan speed can be changed by 

▲ and ▼

 key. 

Note: When one of the heating or cooling mode is selected, 
automatic fan speed is activated. If the automatic fan 
speed is selected, fans operates according to the “Air Qua-
lity or Carbon Dioxide Sensor” value. If sensor is not con-
nected, fan speed is decreased to a minimum value. 

Supply Speed Setting 

Exhaust Speed Setting 

7. ALARMS

Thermal or DPS alarm infor-
mation. For both fan, alarm 
information must be con-
nected in series. All outputs 
are switched off, except 
Damper, when alarm oc-
curs. Contact must be in 

the closed position to eliminate the alarm.

 

Outdoor Air Temperature 

6. FAN LOGIC SETTING

While the device is in the On position, if the  FAN key is 
pressed for 5 seconds, fan logic is changed. 

Continious Fan :  Displayed as  

Cont

 on the panel. Fans will 

work  as  long  as  the  device  is 
in the On position. ( Default ) 

Auto  Fan  :  Displayed  as  

Auto

 on the panel. Fans will 

be  active  while  heating  or 
cooling. In other cases the fan 
output is closed. 

7.1 AL:01 FAN CONTACT ALARM (NC) 

7.2 AL:02 ELEC. HEATER OVER HEAT ALARM (NC) 

All electrical heaters' sa-
fety thermostats, must be 
connected in series. If con-
tact is in the opened posi-
tion, alarm happens. Elect-
rical heater outputs are 
closed. Fans run at maxi-

mum speed. Contact must be in the closed position to 
eliminate the alarm.

 

"Alarm Codes" will appear on the right side of the screen 
in case of alarm. Panel' s backlight is flashed until the 
alarm is eliminated. The device will operate as follows. 

Summary of Contents for ADVANCED J8

Page 1: ...Heater Stages Room Tmp Auto Main Digits Supply Air Fan Speed Auto 5 4 3 2 1 Exhaust Air Fan Speed 1 2 3 4 5 Auto Cooling Ventilation Alarm Notification Auxiliary Digits Heating Mode ON OFF On Off Key MODE Mode Key FAN Fan Key SET Increment Decrement Key WARNING Parts that need to be considered in the screenshots are marked with red circle Please notice the scre enshots KEYPAD and PANEL DESCRIPTION...

Page 2: ...ed is selected fans operates according to the Air Qua lity or Carbon Dioxide Sensor value If sensor is not con nected fan speed is decreased to a minimum value Supply Speed Setting Exhaust Speed Setting 7 ALARMS Thermal or DPS alarm infor mation For both fan alarm information must be con nected in series All outputs are switched off except Damper when alarm oc curs Contact must be in the closed po...

Page 3: ...an speed must be set to Auto When these conditions are met the fan speed is controlled accor ding to the air quality or CO2 sensor value 8 SPECIAL CONTROL FUNCTIONS 8 1 AIR QUALITY OR CO2 CONTROL 7 4 AL 04 FIRE CONTACT ALARM NO If contact is in the closed position alarm happens Supply air fan is closed Exhaust air fan run at maximum speed All out puts are closed except Damper The Panel locked Disc...

Page 4: ...selected in the range of 5 35 C by the and keys Default value 30 C Note 1 Minimum Limit can not be greater than maximum limit Note 2 Maximum Limit can not be lower than minimum limit Note If outdoor air temperature value lower than value set in the service menu the heater stages is activated 9 5 ELECTRICAL HEATER CONTROL SETTINGS Electrical heater can be controlled according to the two different t...

Page 5: ...n the box 4 Make the cable connecti ons as shown below to termi nals on the front panel 5 Attach the clip at the top first and then attach the clip at the bottom 10 MOUNTING INFORMATION 2 x 2 x 0 34 0 75mm Shielded Twisted Pair RS485 Data Com munication Cable must be used Note Press the terminal buttons with the help of a fine tipped pen as shown in the figure Don t apply extreme pressure NOTE DON...

Reviews: