4
Outdoor Control Activate:
Firstly, “Main Parameter”
must be replaced as
“
7
”
,
by the MODE and FAN
keys.
Secondly, “Auxiliary Para-
meter” must be replaced
as
“
2
”
, by the
▲
and
▼
keys.
Setpoint Setting:
Firstly, “Main Parameter”
must be replaced as “
8
”,
by the
MODE
and
FAN
keys.
Secondly, “Auxiliary Para-
meter” must be selected in
the range of “
0-20 °C
”, by
the
▲
and
▼
keys.
(Default value : 15 °C)
Control Activate
Setpoint
MANUAL for JAKKA ADVANCED CONTROLLER
9.3 BMS ADDRESS SETTING
After logging into the servi-
ce menü, using the MODE
and FAN keys, select the 00.
parameter.
Use the
▲
key to increase
the address, use the
▼
key
to decrease the address.
( Setting range 0-247 )
9.4 SETPOINT LIMIT OPERATIONS
Minimum
Limit:
Firstly,
“Main Parameter” must be
replaced as “02”, by the
MODE and FAN keys.
Secondly, “Auxiliary Parame-
ter” can be selected in the
range of 5-35 °C, by the
▲
and ▼
keys.
(Default value: 05 °C)
Maximum Limit:
Firstly, “Main Parameter”
must be replaced as “03”, by
the MODE and FAN keys.
Secondly, “Auxiliary Parame-
ter” can be selected in the
range of 5-35 °C, by the
▲
and ▼
keys.
(Default value : 30 °C)
Note 1:
Minimum Limit can not be greater than maximum
limit.
Note 2:
Maximum Limit can not be lower than minimum
limit.
Note: If outdoor air temperature value lower than value set
in the service menu, the heater stages is activated.
9.5 ELECTRICAL HEATER CONTROL SETTINGS
Electrical heater can be controlled according to the
two different temperature value.
01 : Controlled Depending on Room Temperature :
Electrical heater is controlled by the sensor on the
panel or return air temperature sensor. Control is acti-
ve without any adjustment. ( Default )
02 : Controlled Depending on Outdoor Temperature:
Electrical heater is controlled according to the
“Outdoor Air Temperature Sensor” connected on the
main controller. Enter the service menu to activate the
control according to the outdoor air temperature.
9.8 FACTORY DEFAULT
This parameter used to correct changes made by mis-
take. Firstly, “Main Parame-
ter” must be replaced as
“42”, by the MODE and
FAN keys.
Secondly, “Auxiliary Para-
meter” must be replaced as
“
01
”
, by the
▲
and
▼
keys.
When the device returned factory defaults, parameter
value is set to
“
00
” automatically.
(Default value = 0)