Recuperator

SAFETY

 This product must not be disassembled under any circumstances. Only

   authorized repair technicians are qualified to conduct disassembly and repairs.

 Failure to heed this warning may result in fire, electrical shock or injury.

 Do not install this product in a refrigerated warehouse, heated swimming pool or

  other location where temperature and humidity are significantly different. (Failure

  to heed this warning may result in electrical shock or malfunctioning.)

• 

Do not install this product where it will be directly exposed to rain.

  (Failure to heed this warning may result in electrical shock or malfunctioning.)

 Do not install this product in a location where acid, alkali or organic solvent

  vapors, paints or other toxic gases, gases containing corrosive components or

  high concentrations of oily smoke are present. (Failure to heed this warning may

  result not only in malfunctioning but also fire, power leakage and electrical shock.)

 Do not use this product outside the range of its rated voltage and control capacity.

  JRH72N; Single phase, 220-240V, 50 Hz. (Failure to heed this warning may result in

  fire or electrical shock.)

 Install this product in an environment where the temperature ranges from -10 °C

to +46 °C and the relative humidity is less than 80%. If condensation is expected

to form, heat up the fresh outside air by a duct heater etc.

• 

Select a position for introducing the outside air where no exhaust or combustion

gases will be sucked into the fresh air duct and where it will not be covered by

snow (Failure to ensure a supply of air can result in producing a state of Oxygen

deficiency inside the room.)

 Select an adequately sturdy position for installing the product and install it

properly and securely. (Injury may result if the product should fall.)

 Use the designated electrical wires for the terminal board connections and

connect the wires securely so that they will not be disconnected. (Failure to

ensure proper connections may result in fire.)

 When passing metal ducts through wooden buildings clad with metal laths, wire

laths or metal, these ducts must be installed in such a way that they will not

make electrical contact with metal laths, wire laths or metal sheets.

(Power leakage can cause ignition.)

• 

The outside ducts must be tilted at a gradient(1/30 or more) downwards toward

the outdoor area from the main unit, and properly insulated. (The entry of rain

water may cause power leaks, fire or damage to household property.)

 Gloves should be worn during installation.

(Failure to heed this warning may result in injury.)

 A dedicated circuit breaker must be installed at the origin of mains power supply.

This circuit breaker must be provided with a means for locking (lock and key).

 Connect the product properly to the ground. (Malfunctioning or power leaks can 

  cause electrical shock.)

 An isolator switch having a minimum contact gap of 3 mm in all poles 

  must be provided as a means of disconnecting the power supply.

Summary of Contents for JRH72N Series

Page 1: ...talogu su informativnog karaktera Jakka Group zadržava pravo promene cena i podataka bez prethodne najave Za više informacija pre konačne kupovine kontaktirajte našu prodajnu službu User s Manual for JRH72N series ...

Page 2: ...SEFETY CONTROL LIST COMPONENTS DIMENSIONS TECHNICAL SPECIFICATION INSTALLATION 1 2 3 3 3 4 7 Contents MAINTENANCE TROUBLESHOOTING 8 10 11 ...

Page 3: ...ition for introducing the outside air where no exhaust or combustion gases will be sucked into the fresh air duct and where it will not be covered by snow Failure to ensure a supply of air can result in producing a state of Oxygen deficiency inside the room Select an adequately sturdy position for installing the product and install it properly and securely Injury may result if the product should f...

Page 4: ... air flow Make sure the drain hose is connected and check for any blockages through the drain line If needed clean it Please check that the duct dimensions used in the duct system are correct and of the same dimension of the units duct connection If wrong correct it with appropriate one Make sure electrical connections are done as it is described in this manual Make necessary corrections if there ...

Page 5: ...0 360 1045 1510 170 270 2000 910 1430 430 1045 1510 250 300 2500 1170 1790 425 1300 1870 300 300 3000 1170 1790 515 1300 1870 370 370 4000 1170 1890 515 1300 1970 370 370 5000 1380 1990 645 1455 2070 430 432 6000 1380 1990 645 1455 2070 430 432 800 1000 1500 2000 2500 3000 4000 5000 6000 Mains Connection Working range Air flow rate m h 800 1000 1450 1900 2400 2970 3730 4700 5700 Sound level dB A 4...

Page 6: ...lied in a torque enough to secure a rigid connection The other part is mounted to the wall and used as a hanger to fix the unit Following aspects must be considered during mounting of the unit 1 The appliance must be mounted level 2 The installation space must be freezing free Checking Product Received After receiving the product inspect for any shipping damage Claims for damage either apparent or...

Page 7: ...ure that there is no leakage between the duct connections of the unit and the duct Use a duct tape where necessary Connecting the ducts Fresh air grille EA exhaust air outlet OA outside air intake Service area Exhaust air grille Service space SERVICE AREA A Model Dimensions A mm 800 300 1000 300 1500 430 2000 430 2500 570 3000 570 4000 570 5000 650 6000 650 ...

Page 8: ...st Air or Fresh Air Alternative Air Outlet Alternative Air Outlet Air Inlet Return Air or Outside Air Air Outlet Exhaust Air or Fresh Air Air Inlet Return Air or Outside Air Air Outlet Exhaust Air or Fresh Air Alternate Air Outlet Alternate Air Outlet RIGHT HAND SIDE INSTALLATION LEFT HAND SIDE INSTALLATION Install the drain plug on the side of the fresh air ...

Page 9: ...he air volume from the unit and give rise to abnormal sounds sharp bends Extremely Multiple Bends Bends right next to the outlet Sudden contraction and or expansions in duct diameter The distribution ducts should be connected to the unit through rigid or semi flexible ducts in order to avoid abnormal sounds and vibration Flexible ducts may also be used ensuring that the structure of the duct does ...

Page 10: ...o ensure rotor cannot freewheel Failure to secure drive sheaves or disconnect power before servicing could result in death or serious injury Filter Maintenance WARNING Do not start system without air filters properly installed and inspection doors screwed Otherwise blockages in heat exchanger may occur HOW TO ACCESS FILTERS STEP 1 To open the service door remove out 4 screws on the service cover S...

Page 11: ... on the filter material After it is completely dry mount the filter to the unit close the service door and tighten the screws thoroughly Filter Vacuum Cleaner NOTE It may be handy to keep spare clean and dry filters for quick replacement of dirty filters to minimize unit downtime for filter maintenance Exchanger Maintenance For best performance clean up the air exchanger periodically If the filter...

Page 12: ...ger Clean with hot water or steam Clean the heat recovery exchanger with hot water or steam Use natural detergent or soap powder if need be Leave it to dry after cleaning and mount it to the unit after it is completely dry Tighten the service cover screws thoroughly and make sure the heat recovery exchanger does not fall down ...

Page 13: ...correct phase connection a Filters clogged or dirty a Change or clean filters b Air duct is clogged b Check the air ducts c Channel connections are incomplete c Check the duct system for leaks and complete the connections a Channel connections are incomplete a Check the duct system for leaks and complete the connections b Supply voltage is low b Measure the current drawn by the motor against overl...