background image

KEYPAD AND PANEL DESCRIPTIONS

 

1. ON—OFF OPERATIONS

Use the 

key to Opening/Closing operations.

 

When pressing the button once, the device will switch 
on or off.

 

3. SETPOINT SETTING

Use  the 

  and 

  keys 

to adjust the setpoint. If 
the  keys  are  pressed 
one  time,  setpoint  will 
be  changed  1  °C.  Use 
the 

▲ 

key  to  increase 

the  setpoint,  use  the 

▼ 

key  to  decrease  the  set-
point. 

  Setting  range  5  °

C—

30 

°C.

 

Off Position

 

On Position

 

2. OPERATION MODE SETTINGS

While the device is in the On Position, operation mo-
de can be changed with 

key.

 

Note: The active mode icon flashes on the panel.

 

Heating or Cooling Mode

 

Ventilation Mode

 

4. MONITORING DIFFERENT TEMPERATURES

Setpoint Setting

 

  On/Off Key 

  Mode Key

 

  Fan Key

 

  ▲

 

▼ 

Increment/Decrement Key  

WARNING !! 

 

Parts that need to be considered in the screen shots are 
taken into the circle. Please notice the screenshots.

 

The sensor values, which is measured by main control-
ler, are displayed alternately on the panel. In this appli-
cation 

Room  Temperature,  Supply  Air  Temperature, 

Outdoor  Air  Temperature,  Exhaust  Air  Temperature

” 

sensors can be measured by main controller.

 

Note  1:  If  Room  Temperature  Sensor  is  not  connected  to 
main  controller,  Temperature  Sensor  value  of  the  panel  is 
measured.

 

Note  2:  Supply  Air  Temperature  and  Room  Temperature 
value are measured by same input. If user wants to get  the 
Supply Air Temperature value, ChangeReturntoSupply para-
meter ( Service Menu 11. parameter, BMS 344. parameter ) 
must be set to 

“1”. 

After doing this changing, room tempe-

rature value is measured by panel.

 

Note 3: If Outdoor Air Temperature Sensor is connected and 
necessary  settings are  made,  electrical  heater  is  controlled 
by the Outdoor Air Temperature. Electrical Heater control is 
performed  by  the  Return  Air  Temperature  sensor  value  by 
default.

 

Heating

 

Electrical Heater Stages

 

Room Tmp

 

Setpoint

 

Home İcon

 

Supply Air Fan Speed 

Auto

-

5

-

4

-

3

-

2

-

1

 

Exhaust Air Fan Speed 

1

-

2

-

3

-

4

-

5

-

Auto

 

Air Quality

 

Sup. Air Tmp

 

Cooling

 

Ventilation

 

Out. Air Tmp

 

Alarm Notification

 

Auxiliary Digits

 

Days

 

Auto

 

Main Digits

 

Keylock

 

Exh. Air Tmp

 

MANUAL

 

for

 JAKKA PRO 

C

ONTROL

L

ER

Summary of Contents for Pro

Page 1: ... this appli cation Room Temperature Supply Air Temperature Outdoor Air Temperature Exhaust Air Temperature sensors can be measured by main controller Note 1 If Room Temperature Sensor is not connected to main controller Temperature Sensor value of the panel is measured Note 2 Supply Air Temperature and Room Temperature value are measured by same input If user wants to get the Supply Air Temperatur...

Page 2: ...ion if pressing FAN key for 5 seconds fan logic is changed Continious Fan Displayed as Cont on the panel Fans will work as long as the device is in the On position Default Auto Fan Displayed as Auto on the panel Fans will be active while heating or cooling In other cases the fan output is closed 7 CLOCK SETTINGS When pressing the MODE key for 6 7 seconds hour digit flashes on the panel While digit...

Page 3: ...u re 8 and Exhaust Air Temperature 2 alarm happens Electrical Heater 1 stage opens during alarm When Exhaust Air Tempe rature 2 and time passed up to the OutdoorTempFrostOutTimerLimit BMS 331 parameter alarm is eliminating 9 6 AL 06 OUTDOOR TEMP SEN FROST ALARM 9 3 AL 03 FIRE CONTACT ALARM NO If contact is in the closed position or Room Tempe rature SetFireA larmTemp BMS 343 Service Menu 44 para m...

Page 4: ... 15 C damper is open 2 Outdoor Air Temp Room Temp 3 and Setpoint Room Temp 2 and Outdoor Air Temp 35 C damper is open closed in the other conditions Cooling Mode 1 Outdoor Air Temp Room Temp 3 and Setpoint Room Temp 2 and Outdoor Air Temp 32 C damper is open 2 Outdoor Air Temp Room Temp 3 and Setpoint Room Temp 2 and Outdoor Air Temp 10 C damper is open closed in the other conditions 11 SERVICE ME...

Page 5: ...vice menu to activate the control according to the outdoor air temperature Outdoor Control Activate Firstly Main Parameter must be replaced as 9 by the MODE and FAN keys Secondly Auxiliary Para meter must be replaced as 2 by the and keys 11 6 DATE SETTINGS 1 Firstly Main Parameter must be replaced as 12 by the MODE and FAN keys Secondly Auxiliary Para meter must be set to the desired day value 2 F...

Page 6: ...ons as shown below to termi nals on the front panel 5 Attach the clip at the top first and then attach the clip at the bottom 13 CONTROL PANEL CABLE CONNECTIONS 2 x 2 x 0 34 0 75mm Shielded Twisted Pair RS485 Data Com munication Cable must be used Note Press the terminal buttons with the help of a fine tipped pen as shown in the figure Don t apply extreme pressure NOTE DON T USE THE SCREWDRIVER 12...