7. ÖZEL KONTROL FONKSİYONLARI

11.4 SETPOINT LIMIT OPERATIONS

 

Minimum  Limit: 

Firstly, 

Main  Parameter

” 

must  be 

replaced as 2, by the 

MODE

 

and  

FAN

 keys.

 

Secondly, 

Auxiliary  Para-

meter

” 

can  be  selected  in 

the range of 5

-

35 °C, by the 

  and 

  keys. 

(Default 

value: 05 °C)

 

Maximum Limit:

 

Firstly, 

Main  Parameter

” 

must  be  replaced  as  3,  by 
the 

MODE

 and  

FAN

 keys.

 

Secondly, 

Auxiliary  Para-

meter

” 

can  be  selected  in 

the range of 5

-

35 °C, by the 

 and 

 keys. 

 

(Default value : 30 °C)

 

Note 1: Minimum Limit can not be greater than maxi-
mum limit.

 

Note  2:  Maximum  Limit  can  not  be  lower  than  mini-
mum limit.

 

11.3 BMS ADDRESS SETTING

 

After logging into the servi-
ce men

u

, using the 

MODE

 

and 

FAN 

keys, select the 00. 

parameter.

 

Use  the 

▲ 

key to increase 

the  address,  use  the 

▼ 

key 

to  decrease  the  address. 

Setting range 0

-

247.

 

11.5 ELECTRICAL HEATER CONTROL SETTINGS

 

Electrical  heater  can  be  controlled  according  to  the 
two different temperature value.

 

01 : Controlled Depending on Room Temperature : 

Electrical heater is controlled by the sensor on the pa-
nel or return air temperature sensor. Control is active 
without any adjustment. ( Default )

 

02 : Controlled Depending on Outdoor Temperature:

 

Electrical heater is controlled according to the 

Outdoor Air Temperature Sensor

” 

connected on the 

main controller. Enter the service menu to activate the 
control according to the outdoor air temperature.

 

Outdoor Control Activate:

 

Firstly, 

Main  Parameter

” 

must be replaced as 

9

, by 

the 

MODE

 and  

FAN

 keys.

 

 

Secondly, 

Auxiliary  Para-

meter

” 

must be replaced as 

2

, by the 

 and 

 keys.

 

11.6 DATE SETTINGS

 

1. Firstly, 

Main Parameter

must be replaced as 12, by 
the 

MODE

 and  

FAN

 keys.

 

Secondly, 

Auxiliary Para-

meter

” 

must be set to the 

desired day value.

 

2. Firstly, 

Main Parameter

must be replaced as 13, by 
the 

MODE

 and  

FAN

 keys.

 

Secondly, 

Auxiliary Para-

meter

” 

must be set to the 

desired month value.

 

3. Firstly, 

Main Parameter

must be replaced as 14, by 
the 

MODE

 and  

FAN

 keys.

 

Secondly, 

Auxiliary Para-

meter

” 

must be set to the 

desired year value.

 

Note: When the specified steps are correctly completed, 
device will choose day of week correctly.

 

Setpoint Setting:

 

Firstly, 

Main  Parameter

” 

must  be  replaced  as 

10

by  the 

MODE

  and   

FAN

 

keys.

 

Secondly, 

Auxiliary  Para-

meter

” 

must be selected in 

the range of 0

-

20 °C, by the 

 

and 

 keys.

 

(Default value : 15 °C)

 

Note: If outdoor air temperature value lower than 
value set in the service menu, the heater stages is 
activated.

 

Set

 

Control Activate

 

This parameter used to correct changes made by mista-

ke.

 

Firstly, 

Main  Parameter

” 

must  be  replaced  as  15,  by 
the 

MODE

 and  

FAN

 keys.

 

Secondly, 

Auxiliary  Para-

meter

” 

must  be replaced as 

1, by the 

 and 

 keys.

 

When the device returned factory defaults, parameter 
value is set to "0" automatically. 

(Default value = 0)

 

11.7 FACTORY DEFAULT

 

MANUAL

 

for

 JAKKA PRO 

C

ONTROL

L

ER

Summary of Contents for Pro

Page 1: ... this appli cation Room Temperature Supply Air Temperature Outdoor Air Temperature Exhaust Air Temperature sensors can be measured by main controller Note 1 If Room Temperature Sensor is not connected to main controller Temperature Sensor value of the panel is measured Note 2 Supply Air Temperature and Room Temperature value are measured by same input If user wants to get the Supply Air Temperatur...

Page 2: ...ion if pressing FAN key for 5 seconds fan logic is changed Continious Fan Displayed as Cont on the panel Fans will work as long as the device is in the On position Default Auto Fan Displayed as Auto on the panel Fans will be active while heating or cooling In other cases the fan output is closed 7 CLOCK SETTINGS When pressing the MODE key for 6 7 seconds hour digit flashes on the panel While digit...

Page 3: ...u re 8 and Exhaust Air Temperature 2 alarm happens Electrical Heater 1 stage opens during alarm When Exhaust Air Tempe rature 2 and time passed up to the OutdoorTempFrostOutTimerLimit BMS 331 parameter alarm is eliminating 9 6 AL 06 OUTDOOR TEMP SEN FROST ALARM 9 3 AL 03 FIRE CONTACT ALARM NO If contact is in the closed position or Room Tempe rature SetFireA larmTemp BMS 343 Service Menu 44 para m...

Page 4: ... 15 C damper is open 2 Outdoor Air Temp Room Temp 3 and Setpoint Room Temp 2 and Outdoor Air Temp 35 C damper is open closed in the other conditions Cooling Mode 1 Outdoor Air Temp Room Temp 3 and Setpoint Room Temp 2 and Outdoor Air Temp 32 C damper is open 2 Outdoor Air Temp Room Temp 3 and Setpoint Room Temp 2 and Outdoor Air Temp 10 C damper is open closed in the other conditions 11 SERVICE ME...

Page 5: ...vice menu to activate the control according to the outdoor air temperature Outdoor Control Activate Firstly Main Parameter must be replaced as 9 by the MODE and FAN keys Secondly Auxiliary Para meter must be replaced as 2 by the and keys 11 6 DATE SETTINGS 1 Firstly Main Parameter must be replaced as 12 by the MODE and FAN keys Secondly Auxiliary Para meter must be set to the desired day value 2 F...

Page 6: ...ons as shown below to termi nals on the front panel 5 Attach the clip at the top first and then attach the clip at the bottom 13 CONTROL PANEL CABLE CONNECTIONS 2 x 2 x 0 34 0 75mm Shielded Twisted Pair RS485 Data Com munication Cable must be used Note Press the terminal buttons with the help of a fine tipped pen as shown in the figure Don t apply extreme pressure NOTE DON T USE THE SCREWDRIVER 12...

Reviews: