SELECTION OF SITE
Ø
Proper space should be there for placement and opening of doors of the
Silent DG set.
Ø
There should be atleast 1.5 meter free space around the DG set for
proper operation and maintenance.
Ø
There should be cross ventilation of air to ensure proper cooling of DG
set. Exhaust gases and hot air discharge should not re-circulate inside
the acoustic enclosure (canopy).
Ø
If Genset is to be installed in the room, please ensure proper cross
ventilation and surrounding space.
Ø
There should be no restriction for fresh air suction and hot air discharge.
If 2 nos. DG sets are installed at the site, ensure that hot air outlet of the
one DG set does not become the fresh air intake of the 2nd DG set.
Ø
If Genset is to be installed in the basement, please ensure ventilation
with respect to Air requirement and clear space for every maintenance.
Ø
Distance between two SDG set should be minimum 1.5 meters.
Ø
A low height shelter for the Silent DG Set should be avoided. It should
not obstruct the hot air outlet, shelter height minimum 1.5 meter or
equal to height of genset
Ø
It is preferable to install the DG set in an open area. No shade (roof) is
required over it. However, if the AMF Panel is outside the Acoustic
Enclosure, then a shelter is recommended for the AMF Panel.
Ø
For Roof Top Installation, ensure that the civil structure is capable to
bear the static and dynamic load of DG set. The load of the Silent DG set
should be borne by Columns and Beams of the building.
Ø
Proper space should be there for Earthing.
Ø
If there are no space constraints, the DG set should be placed near the
distribution panel.
Ø
The DG set should be located away from polluted surroundings such as
corrosive fumes, cement dust, fibres, cotton and toxic chemicals to
avoid overheating of the D.G. Set.
Ø
There should be sufficient space around the Genset to avoid resonance
and echo effect which contributes to abnormal sound from Genset.
Ø
The space should be open without any obstacles.
1
JAKSON & CO.