Trouble Shooting
20
JP5535 True Online 1-3K UPS User Manual
under voltage, input
fuse is off
49
Fault: Inverter fault
Inverter over voltage,
inverter under voltage,
Please contact with distributer or
service center.
51
Warn: UPS over
temperature
Environment
temperature is higher
than permitted point,
ventilation is blocked
Please ensure that nothing blocks
ventilation and environmental temp
must be 0~40
C
53
Fault: Fan failure
One or more fans are
failure, fan wires are
loosen
Please contact with distributer or
service center
55
Warn: Inverter
overload
Loads are on inverter
and over the capacity
of the UPS
Remove some loads to ensure that
total loads is under the capacity of
the UPS
57
Warn: Inverter
overload timeout
Load is over the
capacity of the UPS
and timeout, UPS will
transfer to bypass
mode if bypass is
available
Remove some loads to under 95%,
UPS will transfer to inverter
automatically
65
Warn: Battery low
UPS works in battery
and battery voltage is
low
Recover input power or save data
upon “battery low”
71
Fault: Charger
fault
There is no charger
output.
Please contact with distributer or
service center
72
Warn: input over
current
Abnormal large
current enter in
rectifier.
Please contact with distributer or
service center
74
Warn: Manual
shutdown
UPS will shutdown
output or transfer to
bypass mode
/
/
Battery discharge
time diminishes
The battery has not
been fully charged
Charge the battery for more than 10
hours
UPS is overload
Check the loads and remove some
devices