14
Notes:
Please make sure that the input power is three-phase with 4 wires, and the
input voltage is within the allowable voltage range (refer to Appendix 1).
Make sure the input power is the positive phase sequence and battery polarities
are correctly connected;
3.4 Requirements of wiring cables and protect device for JP9960 series UPS
External batteries of JP9960 Series UPS require serial connect positive and negative of
each group of 14-16 batteries (12VDC per battery) with the same capacity, nominal
voltage for each group being168VDC-192VDC. Battery capacity and number of group
can be selected at your option. Battery pack must be equipped with DC switch and input
fuse, and overload and line voltage should also be taken into consideration for wire
diameter selection. Please refer to the table below for details.
Model
Rated power Input live wire
diameter
Output live
wire
diameter
Battery
positive/neg
ative
wire
diameter
Ground wire
diameter
N
wire
diameter
JP9960 20K 20kva/18kw
10AWG/4mm
2
10AWG/4
mm
2
6AWG/10m
m
2
10AWG/4mm
2
6AWG/10m
m
2
JP9960 30K 30kva/27kw
6AWG/10mm
2
6AWG/10
mm
2
4AWG/16m
m
2
6AWG/10mm
2
4AWG/16m
m
JP9960 40K 40kva/36kw
6AWG/10mm
2
6AWG/10
mm
2
1AWG/35m
m
2
6AWG/10mm
2
1AWG/35m
m
2
JP9960 60K 60kva/48kw
2AWG/25mm
2
2AWG/25
mm
2
0AWG/50m
m
2
2AWG/25mm
2
0AWG/50m
m
2
JP9960 80K 80kva/64kw
1AWG/35mm
2
1AWG/35
mm
2
0000AWG/9
5mm
2
1AWG/35mm
2
0000AWG/9
5mm
2