General

Pipe installation must be carried out in accordance with 

current norms and directives.

JAMA Inverter

 can only operate up to a return 

temperature of about 55 °C and an outgoing temperature 

of about 58 °C from the heat pump.

JAMA  Inverter

  is  not  equipped  with  external  shut  off 

valves  on  the  water  side;  these  must  be  installed  to 

facilitate  any  future  servicing.  The  return  temperature  is 

limited by the return line sensor.

Water volumes

When docking with 

JAMA Inverter

 free flow in the climate 

system is recommended for correct heat transfer. This can 

be achieved by use of a bypass valve. If free flow cannot 

be ensured, it is recommended that a buffer tank  is 

installed.

Following

 

water

 

volumes

 

are

 

recommended

-16

-12

-8

JAMA Inverter 

150 l

80 l

50 l

Minimum volume, climate sys-
tem during heating/cooling

150 l

100 l

80 l

Minimum volume, climate sys-
tem during under floor cooling

NOTE

The  pipe  work  must  be  flushed  before  the  heat 

pump is connected, so that any contaminants do 

not damage the components parts.

Pipe coupling heating medium

circuit

 

JAMA Inverter

 can be connected directly to the heating

system see the section "Docking" or according to one 

of the system solutions that can be downloaded from the 

website 

www.kaukora.fi

 

The heat pump must be vented by the upper con-

nection (QM20) using the venting nipple on the 

enclosed flexible hose

.

 

Install the supplied particle filter (HQ1) before the

 

inlet, i.e. the 

connection (XL2, HM-in) on 

JAMA Inverter

.

 

All outdoor pipes must be thermally insulated with

at least 19mm thick pipe insulation.

 

Install shutoff valves (QM31 and QM32) and drain

valves (QM1) so that 

JAMA Inverter

 can be emptied in 

the event of prolonged power failures. Shutoff - (QM31 

and QM32) and drain valve (QM31) are not part of the 

delivery

Tryckfall (kPa)

0

0

0,2

0,4

0,6

0,8

1,0

1,2

0,1

0,2

0,3

0,4

0,5

0,6

Flow l/s

Pressure drop
(kPa)

-8, -12

-16

-EB101

-FL10

XL1

XL2

-RN10 -QM40

-HQ1 -QM41

-QM1

EB101

 

Heat pump

 

FL10

 

Safety valve

 

HQ1

 

Particle filter

 

RN10

 

Trim valve

 

QM1

 

Tapping valve

 

QM40

 

Shut-off valve

 

QM41

 

Shut-off valve

19

Chapter 4 | 

Pipe connections

4  Pipe connections

Summary of Contents for M8

Page 1: ...Installer manual LEK LEK LEK J M Inverter M8 M12 M16 Air water heat pump...

Page 2: ......

Page 3: ...dium circuit Docking alternatives 21 5 Electrical connections 22 General 22 Connections 24 6 Commissioning and adjusting 30 30 30 30 31 32 Preparations Filling and venting the heating medium sys tem C...

Page 4: ...sign or technical modifications are reserved Symbols NOTE This symbol indicates danger to machine or person Caution This symbol indicates important information about what you should observe when main...

Page 5: ...DATA Serial number Caution Always give the product s serial number when reporting a fault Country specific information Installer manual This installer manual must be left with the customer 3 Chapter 1...

Page 6: ...qualified person Fill in the page for information about installation data in the User manual Date Signature Notes Description System flushed System vented Particle filter Shut off and drain valve Cha...

Page 7: ...Contact information 5 Chapter 1 Important information Kaukora Oy PL 21 Tuotekatu 11 21200 Raisio Puh 02 4374 600 E mail kaukora kaukora fi www kaukora fi...

Page 8: ...the neighbours JAMA Inverter must not be placed so that recirculation of the outdoor air can occur This causes lower output and impaired efficiency The evaporator should be sheltered from direct wind...

Page 9: ...is used The section of the pipe that can be affected by frost must be heated by the heating cable to prevent freezing Route the pipe downward fromJAMA Inverter The outlet of the condensation water pi...

Page 10: ...from JAMA Inverter The condensation water pipe must have a water seal to prevent air circulation in the pipe Installation area The distance between JAMA Inverter and the house wall must be at least 15...

Page 11: ...Removing the covers JAMA Inverter M8 LEK JAMA Inverter M12 JAMA Inverter M16 LEK LEK Removing the front panel JAMA Inverter M8 LEK HQ1 9 Chapter 2 Delivery and handling...

Page 12: ...JAMA Inverter M12 LEK HQ1 JAMA Inverter M16 LEK Removing the side panel JAMA Inverter M12 LEK JAMA Inverter M16 DATA LEK Chapter 2 Delivery and handling 10...

Page 13: ...UB3 EP1 X1 EB11 CM 20S 63H1 LPT SM2 SM1 FM01 PWB2 PWB3 PWB1 BT12 BT15 BP4 QN2 BT3 PF3 HS1 EP2 GQ10 QN1 BP2 QM35 QM36 BP1 QN3 CH EB10 LEK DATA XL2 UB1 UB2 W1 XL1 UB3 LEK DATA PF1 PF3 11 Chapter 3 The h...

Page 14: ...1 GQ1 GQ10 QM35 QN3 QM36 TB BP1 QN2 PWB1 PWB2 PWB3 DH UB3 BT3 BP4 PF3 BT15 EP1 EP2 HS1 BP2 BT12 X1 EB11 CM 20S 63H1 LPT SM2 SM1 FM01 CH EB10 LEK DATA XL2 UB1 UB2 W1 XL1 UB3 LEK DATA PF3 PF1 Chapter 3...

Page 15: ...Inverter M16 LEK GQ1 DH X1 CM 63H1 CH SM2 SM1 FM01 PWB2 PWB3 PWB1 QN2 20S BT12 TB BP1 PF3 QN3 BP4 BT3 BT15 UB3 GQ10 HS1 EB10 QN1 EP2 QM36 QM35 EB11 GQ2 FM02 EP1 F LPT BP2 13 Chapter 3 The heat pump de...

Page 16: ...LEK DATA XL2 UB1 UB2 XL1 UB3 W1 LEK DATA PF3 PF1 Chapter 3 The heat pump design 14...

Page 17: ...coming supply AA23 X4 Terminal block communication EB10 CH Compressor heater EB11 DH Drip tray heater F Main fuse compressor unit Fuse for external heating cable 250 mA F3 max 45 W GQ1 FM01 Fan GQ2 FM...

Page 18: ...on EB10 CH Compressor heater EB11 DH Drip tray heater F Main fuse compressor unit Fuse for external heating cable 250 mA F3 max 45 W GQ1 FM01 Fan GQ2 FM02 Fan PWB1 PWB2 PWB3 Control board Inverter boa...

Page 19: ...JAMA Inverter M12LEK EB11 PWB3 PWB1 EB10 AA23 FM01 TB F F3 AA23 X4 AA23 X1 DH CH GQ1 AA23 S2 LEK PWB2 17 Chapter 3 The heat pump design...

Page 20: ...JAMA Inverter M16 LEK PWB3 PWB1 EB10 FM01 AA23 X4 DH CH GQ1 TB AA23 X1 F3 EB11 F AA23 AA23 S2 LEK PWB2 Chapter 3 The heat pump design 18...

Page 21: ...at pump is connected so that any contaminants do not damage the components parts Pipecouplingheatingmedium circuit JAMA Inverter can be connected directly to the heating system see the section Docking...

Page 22: ...JAMA Inverter M8 LEK DATA LEK Heat insulation JAMA Inverter M12 LEK DATA LEK Heat insulation Chapter 4 Pipe connections 20...

Page 23: ...installed in accord ance with current regulations for all docked options See kaukora fi for more docking options Connecting accessories Instructions for connecting accessories are in the install atio...

Page 24: ...t pump should be equipped with a separate one In coming supply must be 230 V 50Hz via distribution boards with fuses If an insulation test is to be carried out in the building disconnect the heat pump...

Page 25: ...JAMA Inverter M12 LEK DH PWB3 CH AA23 FM01 TB F F3 X1 PWB1 AA23 X4 LEK PWB2 JAMA Inverter M16 LEK DH PWB3 CH AA23 FM01 TB F F3 X1 PWB1 AA23 X4 LEK PWB2 23 Chapter 5 Electrical connections...

Page 26: ...ionand orsensortoexternalconnections cables must not be laid closer than 20 cm to high voltage cables when cable routing Power connection JAMA Inverter M8 LEK DATA LEK Incoming supply Power connection...

Page 27: ...JAMA Inverter M12 LEK DATA LEK Incoming supply W1 W1 UB2 UB1 XL1 XL2 UB3 Power connection 25 Chapter 5 Electrical connections...

Page 28: ...nication cable W2 provided by in staller to terminal block AA23 X4 and secure with two cable ties see image For connection of accessory KVR 10 heating cable EB14 is connected via cable grommet UB3 see...

Page 29: ...are routed through ferrite beads EMI filters LEK JAMA Inverter M12 LEK Secure the communication cable W2 here using two cable ties JAMA Inverter M16 LEK Secure the communication cable W2 here using tw...

Page 30: ...4 6 according to following image 5 6 4 2 3 1 WHUQDO JAMA Inverter WHUQDO KHDW FDEOH NOTE The pipe must be able to withstand the heat from the heating cable To ensure this function the accessory KVR 10...

Page 31: ...ck X4 4 6 according to the following image Innemodul X4 GND GND B B A A GND B A AA3 WHUQDO JAMA Inverter For connection of indoor module see relevant manual on www kaukora fi Addressing via cascade co...

Page 32: ...the venting nipple QM20 on the enclosed flexible hose and possibly the cir culation pump 40 Compressor heater JAMA Inverter is equipped with a compressor heater that heats the compressor before start...

Page 33: ...be connected 4 Turn the isolator switch on 5 Ensure that the JAMA Inverter is connected to the power source 6 After 6 8 hours the communication cable W2 is connected to terminal block AA23 X4 7 Resta...

Page 34: ...de Air is initially released from the hot water and venting may be necessary If bubbling sounds can be heard from the heat pump the circulation pump and radiat ors the entire system will require furth...

Page 35: ...r adjusting hot water charging are in the installation manual for the respective indoor section See page 38 for the list of the indoor sections and ac cessories that can be used with JAMA Inverter 33...

Page 36: ...o the hot water heater Large hot water consumption Wait until the hot water has heated up Incorrect settings in the JAMA indoor module See the manual for the indoor module Low room temperature Closed...

Page 37: ...Connection to card PWB1 Sensor placement JAMA Inverter M8 LEK EB11 EB10 GQ1 PWB1 BP1 QN2 QN3 QN1 BP2 SM1 SM2 LPT FM01 DH 20S CH 63H1 35 Chapter 7 Disturbances in comfort...

Page 38: ...erature sensor hot gas BT15 Temperature sensor fluid pipe BT16 Tho Temperature sensor heat exchanger 1 R1 BT17 Tho S Temperature sensor suction gas BT28 Tho A Temperature sensor ambient EB10 CH Compre...

Page 39: ...VDC Resistance kOhm Temperature C 3 256 351 0 40 3 240 251 6 35 3 218 182 5 30 3 189 133 8 25 3 150 99 22 20 3 105 74 32 15 3 047 56 20 10 2 976 42 89 5 2 889 33 02 0 2 789 25 61 5 2 673 20 02 10 2 5...

Page 40: ...ehowatti 21 Part no 5058536 Wall mounting Wall mounting JAMA Inverter M8 Wall mounting JAMA Inverter M12 Water heater Accumulator tank BUFFER 100 Part no 5360118 BUFFER 200 Part no 5360119 JASPI BUFFE...

Page 41: ...400 670 100 365 225 422 965 1035 95 15 90 40 Adjustable 40 50 Accessory KVR 10 is required JAMA Inverter M12 50 255 St llbar 40 50 955 243 512 110 395 265 50 452 1075 1145 108 40 14 85 Adjustable 40...

Page 42: ...Accessory KVR 10 is required 150 mm Fritt utrymme bakom Min avst nd 600 mm 3000 mm 400 mm 600mm Minimalt fritt utrymme Minimalt fritt utrymme Fritt utrymme Free space behind Free space in front Minimu...

Page 43: ...bricks differences in ground level etc and should therefore only be seen as guide values JAMAInverteradjuststhefanspeeddependingonthe ambient temperature and evaporation temperature 2 m 6 m 10 m 2 m...

Page 44: ...3 50 27 18 C Output data according to EN14511 T5K Specified supplied power EER 13 04 4 53 2 88 9 45 3 41 2 77 7 10 2 65 2 68 35 7 C 15 70 5 04 3 12 11 20 3 58 3 12 9 19 2 98 3 08 35 18 C Electrical d...

Page 45: ...Weight excl packaging Miscellaneous IP 24 Enclosure class dark grey Colour 1 Max permitted impedance in the mains connected point in accordance with EN 61000 3 11 Start currents can cause short voltag...

Page 46: ...rature Supply temperature Return temp During shorter time it is allowed to have lower working temperatures on the water side e g during start up Working range compressor operation cooling JAMA Inverte...

Page 47: ...Electrical circuit diagram JAMA Inverter M8 Chapter 9 Technical data 46 Kaukora Oy...

Page 48: ...INV PWB2 OR GR 1 F P BK BK 4A 2 3 Tho P BP1 63H1 BT14 Tho D BT16 Tho R1 BT17 Tho S BT28 Tho A BP2 LPT 20S QN2 EB10 CH EB11 DH 47 Chapter 9 Technical data...

Page 49: ...JAMA Inverter 12 Chapter 9 Technical data 48 Kaukora Oy...

Page 50: ...Y 2 WH 1 WH RD BK CNIP Y Tho P BK BK OR CNFAN1 WH BL 7 BR 6 WH 5 4 RD 1 CNH BR BP1 63H1 Two fan unit only Two fan unit only BK BK CNS RD CNR WH CNF BK BL BL EB10 CH BR BR BT14 Tho D BK BK BT16 Tho R1...

Page 51: ...JAMA Inverter 16 Chapter 9 Technical data 50 Kaukora Oy...

Page 52: ...WH 1 RD CNEEV2 RD CNPS RD CNB RD 6 BL 4 OR 3 Y 2 WH 1 WH RD BK CNIP Y Tho P BK BK OR CNFAN1 WH BL 7 BR 6 WH 5 4 RD 1 CNH BR BP1 63H1 Two fan unit only BK BK CNS RD CNR WH CNF BK BL BL EB10 CH BR BR B...

Page 53: ...n to rear side standard or underneath al ternative 24 External heating cable KVR 10 28 F Filling and venting the heating medium system 30 I Important information 2 Safety information 2 Inspection of t...

Page 54: ......

Page 55: ...Kaukora Oy PL 21 Tuotekatu 11 21200 Raisio Puh 02 4374 600 E mail kaukora kaukora fi www kaukora fi...

Reviews: