Specifications
Storage temperature
-4°F to 131°F (-20°C to 55°C)
Operating temperature
32°F to 113°F (0°C to 45°C)
Humidity
90% maximum Non-condensing
Weight
2.6 lb (1.2 kg)
Size
9” x 7” x 4 3/4” (22.8 cm x 17.7 cm x 11.5 cm)
Protection index
IP 66
Warranty
2 years
POWER SUPPLY
Operational voltage range (SW1 @ 115V)
92 to 125VAC
Operational voltage range (SW1 @ 230V)
184 to 250VAC
Operational frequency range
45 to 65 Hz
Power supply circuit consumption (CPU
Board)
20 W maximum
Fuse 250mA,
250VAC
PROBE INPUT
Temperature probe
2004-10K
Maximum wire length
500 feet (150 m)
Recommended wires
2 conductors, stranded, shielded, AWG #22
ALARM RELAY
Maximum current
1 A at 30VDC
OUTPUT RELAYS
Maximum Current
1HP @ 240VAC, 1/2HP @ 120VAC,
12A@240VAC
Caution Notice
These relays are rated by UL and CSA at 1HP
@ 240VAC, 1/2HP @ 120VAC. However, for
outputs requiring frequent activation it is
recommended not to use more than 1/2HP @
240VAC, 1/4HP @ 120VAC per relay.
Important Notice.
-
It is important to have a backup system in case of a system failure.
-
Low-voltage and high-voltage wire must be passed through different
conducts at least 1 foot (30 cm) apart. If low-voltage and high-voltage
conduits must be crossed, the crossing must be at a 90-degree angle.
-
All wiring must be made by a certified electrician and conform to local
electrical regulations.
Summary of Contents for JD-N2
Page 3: ...JD N2 WIRING DIAGRAM JD N2 Section A 3 WIRING DIAGRAM JD N2 SECTION A ...
Page 6: ...JD N2 INSTALLATION JD N2 Section B 6 INSTALLATION JD N2 SECTION B ...
Page 19: ...JD N2 USER S GUIDE JD N2 Section C 19 USER S GUIDE JD N2 SECTION C ...
Page 20: ...JD N2 USER S GUIDE JD N2 Section C 20 Control Description 7 3 3 5 1 2 3 4 6 ...
Page 28: ...JD N2 INDEX WARRANTY JD N2 Section D 28 INDEX WARRANTY JD N2 SECTION D ...