JD-N2
WIRING DIAGRAM
JD-N2
Section A-5
JD-N2
Electrician’s notes
wiring tips and hints (see guide for details)
(PROBE WIRING) SHIELDED WIRE AWG #22, 500ft (150m) MAXIMUM
LENGTH.
HIGH VOLTAGE WIRE INSTALLED ACCORDING TO LOCAL WIRING CODE.
INSTALL LOW VOLTAGE WIRES (PROBES, COMPUTER LINK OR
POTENTIOMETER WIRES) AT LEAST 12in. (30cm) AWAY FROM HIGH
VOLTAGE WIRES (120/230VAC, 24VDC). ALWAYS CROSS HIGH AND LOW
VOLTAGE WIRES AT A 90-DEGREE ANGLE.
RELAYS: 12A @ 240VAC RESISTIVE, MOTOR 1HP @ 240VAC, 1/2HP @
120VAC AT EACH OUTPUT.
1 WIRE ONLY PER GREEN TERMINAL. USE WIRE CONNECTOR IF YOU
WANT TO CONNECT MORE THAN 1 WIRE, NO BIGGER THAN AWG #12,
NO SMALLER THAN AWG #28.
CHECK INSTALLATION GUIDE FOR ALARM WIRING.
USE SHIELD FOR SHIELDING PURPOSE ONLY. CONNECT THE SHIELD TO
GROUND PLATE
. NEVER LEAVE THE SHIELD UNCONNECTED AT BOTH
ENDS. NEVER CONNECT BOTH ENDS OF THE SHIELD TO GROUND
PLATE
. THE USE OF A SHIELD FOR ALL PROBES IS
MANDATORY
.