Identify cords coming from motor
Control Wiring Instructions:
• For dry contact ON/OFF control, connect dry contact from STOP/
RUN to signal ground.
- Closed contact is motor ON, open contact is motor OFF.
- Connect STOP/RUN wire to signal ground wire if dry contact
ON/OFF control is not used.
• Use the two 4-20ma IN wires for analog current speed control.
- Leave 4-20ma wires disconnected if not used, (less than
5.6ma is OFF).
• 0-10V in to signal ground for analog voltage speed control,
(less than 1V is OFF).
- Connect 10V OUT wire to 10V IN wire for no speed control,
(full speed).
• Use four conductor 26AWG (or heavier), shielded, dual twisted
pair, signal wire with drain wire from J&D control to Permanent
Magnet fan.
• Use the two 4-20ma IN wires for analog current speed control.
- Leave 4-20ma wires disconnected if not used, (less than 5.6ma is OFF).
IS295-20H
J&D Manufacturing • 6200 Hwy 12 • Eau Claire, WI 54701 • 1-800-998-2398 • www.jdmfg.com
Page 12/12
Single Phase Wired for 190-240v
White
Motor to
Power
Black
Green
L1
L2
Ground
Three Phase Wired for
190-240v / 380-460v
Red
White
Black
Green
Motor to
Control
0-10V IN
+10V OUT
Signal
Ground
STOP/RUN
Red
White
Black
Green
Motor to
Power
L1
L2
L3
Ground
DISCONNECT POWER
BEFORE INSTALLING OR SERVICING.
ALL ELECTRICAL WORK SHOULD BE COMPLETED BY
QUALIFIED PERSONNEL AND MEET NATIONAL (NEC),
REGIONAL AND LOCAL ELECTRIC CODES.
!
!
White w/Green Stripe
Orange w/White Stripe
Motor to
Control
+10V OUT
0-10V IN
Green w/White Stripe
STOP/RUN
White w/Orange Stripe
Signal
Ground
White w/Blue Stripe +
4-20ma IN
4-20ma IN
Blue w/White Stripe –
Control
Power
Maintenance Instructions:
• Disconnect power before cleaning or maintaining your fan in order
to prevent serious injury or death.
• Service and repair of fan should only be completed by a qualified
technician.
• For maximum efficiency and fan life, keep the following free from
dirt and dust: blades, damper doors, motor and guard.
• The totally enclosed air over motor has sealed ball bearings and
does not require additional oil.
General Wiring Instructions:
• Wiring should only be performed by a trained electrician to prevent
injury or death.
• Install manual disconnect switch inside building adjacent to fan.
• Route wire to motor with drip loop and secure. Drip loop will drain
accumulated moisture away from the motor.
• Configure internal wires to match supply voltage and wire accord-
ing to motor nameplate. Test to verify correct rotation.
• Only permit power to unit when guards are properly installed to
prevent injury.