Issue: 01.03.2016
Page 8
9.
Installation
Wall drillings for direct ducting of unit.
1.
Drill the wall fixing points and the hole
for the air inlet duct, following the
dimensions as shown on the left or
follow template supplied.
2.
Recommended drill dimension is 157mm
diameter for the air inlet duct.
3.
Attach required length of 150mm Ø
ducting to air spigot and seal joint with
duct tape or silicon.
4.
Pass ambient air probe down inside of
ducting. Coil and cable tie excess cable
neatly.
5.
Remove the top cover of unit for access
to fixing holes, and fix to wall.
6.
Fix the 2 brackets, one each side of unit
using M5 screws and fix to wall.
7.
Seal ducting to hole and fix external air
grille to ducting.
8.
Position ambient air sensor.
Alternative mounting arrangement for
ambient cooler
Spigot can be placed at bottom of unit to
enable external ducting to be used. This is
the alternative arrangement of the unit
where the rear hole is blanked by plate.
Note :
1.
The hole through wall can be drilled in
another location.
2.
Ducting is not provided.
•
Room Air Balance
As the unit can provide up to approximately 700m³/h of airflow into the cellar, this will need to be balanced by allowing air outlet
from the room. This can be done by fitting an air grille in the cellar door (provided in the optional installation kit) or by other means.