background image

Page 7

5.  Drill out a ½" hole and insert the round seal supplied 

with the kit. A remote cable will run through the middle 
hole of the backplate and into the electrical box.

2.5 

Installation of the Backplate on a Flat 
Wall

 

 CAUTION

Do not expose the user interface to direct sunlight. Too 
much direct sunlight will darken the LCD screen, and it 
will no longer be readable.

1.  Turn off the pump at the control panel.

2.  Turn off all electrical power to the pump at the main 

junction box or at the circuit breaker providing electrical 
power to the pump.

  WARNING

ELECTRICAL SHOCK HAZARD

Turn off all switches and the main breaker in the ePump™ 
electrical circuit before starting the procedure. Failure to 
comply may cause a shock hazard resulting in severe 
personal injury or death.

3.  A minimum of two (2) fasteners (installer supplied) are 

required when installing to a flat wall to hold the user 
interface securely.

4.  The backplate has ten (10) mounting holes to choose 

from. Only drill out the plastic film from the holes to be 
used. See Figure 2.

5.  Mark the hole locations on the wall and use the fastener 

to secure the backplate to the wall.

6.  At the bottom of the backplate, cut the two (2) tabs 

out with an appropriate tool, such as a carton cutter or 
an exacto knife, and route the cable through the open 
channel.

2.6 

Connection to the Jandy ePump

TM

 

Variable Speed Pump

The following steps provide the procedure for installing the 
user interface to a Jandy ePump™ variable speed pump.

1. 

Turn off all switches and the main breaker that 
supplies power to the pump.

  WARNING

ELECTRICAL SHOCK HAZARD

Turn off all switches and the main breaker in the pump 
electrical circuit before starting the procedure. Failure to 
comply may cause a shock hazard resulting in severe 
personal injury or death.

2. 

Remove the cover of the pump junction box.

3. 

Feed the RS-485 cable into the  tting.

NOTE 

The user interface uses a four-wire RS-485 interface 
to communicate with the ePump™.

4. 

Unplug the RS-485 connector from the pump.

5. 

Attach the four (4) wires in the RS-485 cable to the 
RS-485 connector. Make sure the colors match the 
positions on the connector. See Figure 2.

6. 

Connect the RS-485 connector back into the pump.

7. 

Set the DIP switch settings for the pump controller 
with the 1 and 2 in the ON position and 3 and 4 in 
the OFF position. See Figure 3.

8. 

Turn on all switches and the main breaker feeding 
power to the pump.

9. 

Verify the operation of the controller. If the 
controller displays 

FAULT PUMP NOT 

CONNECTED

, re-check the wiring and the DIP 

switch address setting on the pump.

Jandy ePump

¥

(Rear View)

RS485

4 3 2 1

REMOTE CONTROL

  5 4 3 2 1

User Interface
(Rear View)

RS485 Cable

2   BLACK

3   

YELLOW

1   RED

4   GREEN

4-Position

DIP Switch

SW 1

SW 2

SW 3

SW 4

Figure 3. 

Wiring the User Interface to the Jandy 
ePump

TM  

Variable Speed Pump

2.7 

Jandy ePump™ Variable Speed 
Pump Switch Settings

For the ePump™, the 4-position dip switch is located at the 
rear of the pump, as shown in Figure 3.

This dip switch serves two functions, it determines what 
type of control will be used with the pump and it selects the 
pump address. The SW 1 (switch 1) and SW 2 are turned ON 
if the pump is to be controlled by a stand alone controller or 
OFF if the pump is to be controlled by the AquaLink

®

 RS or 

AquaLink

®

 PDA.

SW 1

SW 2

CONTROL

OFF

OFF

  AquaLink

®

 RS

  AquaLink

®

 PDA

ON

OFF

OFF

ON

ON

ON

Stand Alone

The SW 3 and SW 4 are turned ON/OFF to select the Pump 
address.

SW 3

SW 4

PUMP No.

OFF

OFF

1

ON

OFF

2

OFF

ON

3

ON

ON

4

Summary of Contents for ePump

Page 1: ...serviced by a professional pool spa service technician The procedures in this manual must be followed exactly Failure to follow warning notices and instructions may result in property damage serious i...

Page 2: ......

Page 3: ...d Stop 9 3 4 Pump Speed Setting 9 3 5 Timeclock Setup and Operation 10 Section 4 Service Setup Options 11 4 1 Entering Service Setup 11 4 2 Minimum and Maximum Pump Speeds 11 4 3 Load Defaults 11 4 4...

Page 4: ...broken or missing Never replace a suction fitting with one rated less than the flow rate marked on the equipment assembly WARNING To Reduce the Risk of Injury a The water in a spa should never exceed...

Page 5: ...trant dans une cuve de relaxation et en sortant Pour viter l vanouissement et la noyade ventuelle ne prendre ni drougue ni alcool avant d utiliser une cuve de relaxation ni quand on s y trouve Les fem...

Page 6: ...crews 6 Plastic Film Additional materials are required for the installation of the user interface and must be supplied by the installer 1 A cable to connect the pump to the remotely mounted user inter...

Page 7: ...ump electrical circuit before starting the procedure Failure to comply may cause a shock hazard resulting in severe personal injury or death 2 Remove the cover of the pump junction box 3 Feed the RS 4...

Page 8: ...o comply may cause a shock hazard resulting in severe personal injury or death 2 Install the normally closed reman s switch to the timeclock assembly See timeclock manufacturer s instructions for deta...

Page 9: ...rted from the controller Manual operation of speeds eStar through 4 differs from manual operation of speeds 5 through 8 NOTE When starting the pump the pump will first run at the priming speed for the...

Page 10: ...UN mode 2 3 4 ePUMP MENU 2 PRESET 2 TIMECLOCK ENABLE 3 5 2 Timeclock Operation When the pump is stopped the associated green LED will illuminate indicating a timeclock program is enabled for that spee...

Page 11: ...enu press and hold MENU then press and hold the and preset 4 keys Hold all three 3 keys down for five 5 seconds To exit press any preset button 2 3 4 ePUMP MENU PRESS PRESET OR MENU 12 00AM PUMP IS OF...

Page 12: ...ing the arrow keys set the priming speed to the desired value Press MENU to accept and store 2 3 4 PRIMING SPEED RPM 3450 ePUMP MENU To set priming duration select PRIMING DURATION using the arrow key...

Page 13: ...s time the ePump controller does not support other types of pumps Section 5 User Set Up Options NOTE The ePumpTM user interface must be in the OFF mode before entering the user setup mode While in set...

Page 14: ...keys select the desired operating mode for the display backlight LIGHT OFF Turn off display backlight LIGHT ON Turn on display backlight 2 MIN TIMEOUT Turn on display backlight with automatic turn of...

Page 15: ...s not affected when LOAD DEFAULTS is executed 8 Key that is pressed to wake up display is also acted upon 9 Press and hold MENU eStar and 4 simultaneously for 5 seconds to enter 10 Setting not saved i...

Page 16: ...lished minimum and maximum specifications 7 Use of non factory authorized parts or accessories in conjunction with the product s 8 Chemical contamination of combustion air or improper use of sanitizin...

Reviews: