background image

Page 12

SECTION 3.
Operating Instructions

3A. Start-Up Procedure

Full lighting and shutdown instructions are

found on the label attached inside the service door of
the heater and in the user's instructions.

WARNING

Flue pipes, draught divertors, hoods, tops,
and water fittings get hot! These surfaces can
cause serious burns. Do not touch these
surfaces when the heater is operating. For
external installations, the addition of an out-
door flue terminal assembly will reduce the
temperature on the top.

WARNING

Keep all objects off the top of the heater.
Blocking air flow could cause a safety hazard,
damage to the heater, and may void the
warranty.

WARNING

LP Models: To avoid possible injury, fire and
explosion, read and follow these precautions
and all instructions on this heater before
lighting the pilot. This heater uses LP gas
which is heavier than air and will remain at
ground level if there is a leak. Before lighting,
sniff at ground level. If you smell gas, follow
these rules:
1. DO NOT light matches. DO NOT turn

electric lights or switches on or off in area.
DO NOT use an electric fan to remove the
gas from area.

2. Shut off gas at LP tank and gas service

cock.

3. Telephone gas company for instructions.

Give your name, address and phone
number.

If your LP tank runs out of fuel, turn off gas at
the heater. After the tank is re-filled, the heater
must be relit in accordance with the
instructions found on the inside of the door.
DO NOT attempt repairs on the gas control or
heater. Tampering is dangerous and voids all
warranties.

1. Clean the pool filter.

2. With the filter pump off, remove the drain

plug. The plug is found on the right side of
the heater.

3. Replace the drain plug with a thermometer

inserted through a temperature and pressure
fitting  (Pete's Plug) (see Figure 14).

4. If there is a manual bypass valve installed,

close it.

5. Make sure the heater is off by moving the

rocker switch to the OFF position.

6. Start the filter pump and wait 3 minutes.

7. Record the thermometer reading (this repre-

sents pool water temperature).

8. Turn the heater on following the lighting and

shutdown instructions found on the inside of
the control compartment.

9. Let the heater run for at least 5 minutes

before recording the new thermometer
reading.

10. If the temperature reading is outside the

minimum/maximum numbers shown in Table
7, gradually open the manual bypass valve
until the temperature rise is obtained (the
temperature rise is the difference between
the temperature reading with the heater off
and the  temperature readings with the
heater running for several minutes.

11. Be sure the thermometer reading remains

steady for at least 3 minutes.

Figure 15.  Heater piping.

Optional

Check Valve

Manual

By-Pass

Valve

Plastic

Pipe

NOTE: When using metal
pipe as heat sink, join
metal and PVC/CPVC,
using metal male and
PVC/CPVC female
connection.

Summary of Contents for Laars Lite 2 LG

Page 1: ...e Carbon Monoxide detectors in the vicinity of this appliance and in any adjacent occupied spaces Improper installation and or operation will void the warranty H0208700GInstallation and Operation Data...

Page 2: ......

Page 3: ...Procedure 12 3B Temperature Control 13 3C Lighting and Shutdown 13 3C 1 Lighting the Heater 13 3C 2 Relighting the Heater 14 3C 3 Shut Down Procedure 14 3C 4 Putting the Heater in Operation Commission...

Page 4: ......

Page 5: ...G Gas LPG Gas LPG Gas LPG Gas LPG Heat Input Gross kW 36 6 36 6 51 3 51 3 79 6 75 0 103 4 97 4 117 2 117 2 Heat Input Net kW 33 0 33 7 46 2 47 2 71 7 69 0 93 2 89 6 105 6 107 8 Heat Output kW 28 4 28...

Page 6: ...r Flow l min 75 7 75 7 94 6 113 6 113 6 Maximum Static Head bar 5 1 5 1 5 1 5 1 5 1 Maximum Outlet Temp C 40 40 40 40 40 Dry Weight kg 84 91 103 114 128 Gas Connection 3 4 in Bsp 3 4 in Bsp 3 4 in Bsp...

Page 7: ...ed to European requirements for use only as a swimming pool or spa heater The LG heater must not be used for any other purpose and must be installed and serviced by a qualified professional The LG hea...

Page 8: ...f the heater remove it 3 Remove all hex head screws fastening the top and lift the top assembly straight up see Figure 2 4 Removethescrewholdingtherainshieldtotherear of the heater Remove the rainshie...

Page 9: ...le into the front compartment then pull thermostat bulb assembly through same hole Figure 3 Flue collector holddown brackets Figure 4 Temperature sensing bulb Caution It may be necessary to have help...

Page 10: ...lue gases which could result in severe injury property damage or death Place the heater in an area where leakage of the heater or connections will not result in damage to the area around the heater or...

Page 11: ...clearance on all sides for inspection see Table 4 Page 7 service and to provide adequate air circulation for proper operation Make sure that the location of the heater complies with the requirements d...

Page 12: ...e System Indoor Connect the draught divertor to a flue system of at least the same diameter and end at least 0 61 meters above the highest point of the roof or other object that is within 3 meters of...

Page 13: ...ervicing purposes see Figure 9 Before operating the heater test for gas sound ness in accordance with the publications listed in Table 3 Do not use a naked flame If the supply gas pressure is less tha...

Page 14: ...gure 13 Do not install any other valve or variable restriction in the piping between the heater outlet and the pool unless it is necessary to increase back pressure or is being used as a diverter valv...

Page 15: ...filter system is 1 m or more above the top of the heater jacket NOTE Do not make the pressure switch adjustment if the heater is installed more than 4 6 m below or 1 9 m above the pool surface Consult...

Page 16: ...the tank is re filled the heater must be relit in accordance with the instructions found on the inside of the door DO NOT attempt repairs on the gas control or heater Tampering is dangerous and voids...

Page 17: ...d phone number DO NOT attempt repairs on the gas control or heater Tampering is dangerous and voids all warranties When lighting or relighting the pilot always turn the temperature control to its lowe...

Page 18: ...and adjusted 4 Remove the blanking screw in the manifold burner setting pressure test nipple see Figure 18 and securely connect a suitable gas pressure gauge 5 Light the heater and allow it to operat...

Page 19: ...the gas supply fails to shut off turn off the main burners only You can either position the rocker switch to OFF or open the service door and press the red button on the gas control For a complete shu...

Page 20: ...opper tubing see Figure 21 6 Use compressed air to blow out any standing water in the heat exchanger In areas subject to only short freeze periods turn off the heater and run the filter pump continuou...

Page 21: ...k Reset it to the 25 C level a day or so before you plan to use the pool 6 During the winter and when on holiday for longer than a week follow the instructions in Section 3 to shut down the heater 7 W...

Page 22: ...p the heater performing properly SECTION 4 Maintenance 4A Gas Pressure Tests Use the following procedures to test the inlet gas pressure see Figure 23 A manometer kit is available from Zodiac Pool Sys...

Page 23: ...properly adjusted the heater should come on about 10 seconds after the filter pump is started and shut off right after the pump shuts off It may be necessary to repeat these steps to get a proper sett...

Page 24: ...er panel and the three screws attaching the manifold bracket 5 Slide the burner tray out of the heater see Fig 26 NOTE Due to the sharp edges on the metal burner wear protective gloves for the next st...

Page 25: ...changer tubes The easiest way to determine the degree of scale buildup is to periodically inspect the tubes Perform this inspection after 60 days of operation and after 120 days of operation This will...

Page 26: ...the following steps 1 Remove the front and rear headers from the tube assembly see Section 2 2 Remove the tube baffles by first removing the spring retaining clip then lifting out the baffles 3 Clean...

Page 27: ...nstallation and or operation can cause nausea or asphyxiation from carbon monoxide in flue gases which could result in severe injury property damage or death Improper installation and or or operation...

Page 28: ...rd see Fig 36 9 Replace heater top and all eight screws see Fig 37 10 Slide the adapter plate up over the bottom of the stack extension Fit the stack extension on top of the collar of the flue transit...

Page 29: ...or the Model LG Lite 2 pool and spa heaters contact your nearest Jandy dealer or distributor If they cannot supply you with what you need contact the techical support department at Zodiac Pool Systems...

Page 30: ...stat only All E0155300 51 Capillary Cover and Insulation All R0356000 52 Sensor Cover and Insulation All R0356100 VENT SYSTEM 53 Top Filler Plate 125 400 R0343701 05 54 Top Enclosure 125 400 R0356201...

Page 31: ...15 19 16 14 18 17 21 32 31 23 25 30 29 24 26 27 26 28 34 35 36 38 37 39 45 42 44 41 40 46 47 49 48 51 50 53 56 58 55 60 59 57 54 68 70 73 71 69 65 72 62 67 67 61 64 65 66 77 75 74 76 74 74 76 87 88 86...

Page 32: ...Nature2 products 8 Abuse damage during transit or installation mis handling tampering vandalism alterations accidents fires floods storms earthquakes power surges lightning pets or other animals inse...

Reviews: