Page 12
Legacy
™
Model LRZM Pool/Spa Heater Installation and Operation Manual
and combustion air are essential for the safe and
ef
fi
cient operation of the heater (See Section 3). An
approved draft hood may be purchased from your local
Jandy distributor. See Section 11 (Parts List) of this
manual for the correct part number for your model and
size heater.
Section 3. Venting
3.1 Combustion
Air
Supply
The heater location must provide suf
fi
cient
air supply for proper combustion and ventilation of
the surrounding area as outlined in the latest edition
of ANSI standard Z223.1 or in Canada, CAN/
CSA-B149.1, and any local codes that may be appli-
cable.
In general, these requirements specify that the
room in which a heater is installed should be provided
with two permanent air supply openings; one within
12 inches (305mm) of the ceiling, the other within
12 inches (305mm) of the
fl
oor. All indoor installa-
tions must have openings to outside air for combus-
tion, ventilation, and dilution of
fl
ue gases from inside
the building (see Figure 5 and Table 3). Zodiac Pool
Systems, Inc. does not recommend indoor installations
that do not provide combustion air from outside the
building.
All outdoor shelter installations (Canada only)
must have uninterrupted openings to outside air for
combustion and ventilation. The installation must
be in accordance with the latest edition of CAN/
CSA-B149.1. Zodiac Pool Systems, Inc. does not
recommend outdoor shelter installations that depend
on internal air for combustion. Combustion air should
be ducted to the heater from outside the structure.
Outside Air Supply:
When combustion air
is supplied directly through an outside wall, each
opening should have a minimum free area of one
square inch per 4,000 BTU/h (1.2kW) input of the
total input rating of all appliances in the enclosed
area. If air is provided through horizontal ducts, each
opening and duct must provide one square inch of
fl
ow
area for each 2000 BTU/h (0.6 kW). These require-
ments are summarized in Table 3. Note that the areas
speci
fi
ed are net free areas and should be increased by
50 percent when the openings are covered by screens,
louvers, grills or other protective covers (see Figure 5
and Table 3).
NOTE
In Canada, follow Canadian Standard, CAN/
CSA-B149.1 or local codes.
Exhaust Fans or Vents:
Any equipment
which exhausts air from the room where the heater
is installed can deplete the combustion air supply or
reverse the natural draft action of the venting system.
This could cause
fl
ue products to accumulate in the
3)
Notes:
1. Use approved
roof jack.
Figure 5. Indoor Installation Venting (USA), or Outdoor Shelter (Canada)
Table 3. Air Openings to Outside
Required Net Free Open Area*
for Combustion Air Openings
*Area indicated is for one of two openings; one at
fl
oor level and
one at the ceiling, so the total net free area would be double the
fi
gures indicated. For special conditions, refer to NFPA54 ANSI
Z223.1.
In Canada refer to the National Standard CAN/CSA-
B149.1 which differs from this table.
Note: If using screens and/or metal louvers, compensate by adding
50% additional area to each opening. If using wood louvers each open-
ing must be at least four times the area indicated in the table above.
Model
Direct from outside
Duct from outside
in
2
cm
2
in
2
cm
2
125
32
206
64
413
175
44
284
88
568
250
63
406
126
813
325
82
429
164
1058
400
100
645
200
1290
Summary of Contents for Legacy LRZM
Page 2: ......