pool, spa or hot tub structure and to all electrical
components and equipment associated with the
pool/spa water circulation system.
2.
The bonding must be accomplished by using a
solid copper conductro, No. 8 AWG or larger.
In Canada No. 6 AWG or larger must be used.
Bond the motor using the external bonding lug
provided on the motor frame.
To avoid the risk of property damage, severe
personal injury, and/or death, always disconnect
the power source before working on a motor or its
connected load.
WARNING
To avoid the risk of property damage, severe per-
sonal injury, and/or death, make sure that the con-
trol switch or time clock is installed in an accessible
location so that in the event of an equipment failure
or a loose plumbing fitting the equipment can be
turned off. This location must not be in the same
area as the pool pump, filter, and other equipment.
WARNING
The pump must be permanently connected to a
dedicated electrical circuit. No other equipment,
lights, appliances or outlets may be connected to
the pump circuit, with the exception of devices that
may be required to operate simultaneously with the
pump, such as a chlorinating device or heater.
WARNING
3.2.3 Electrical Wiring
To avoid risk of property damage, severe personal
injury, or death, always ground before connecting to
an electrical power supply.
WARNING
1.
The pump motor must be securely and
adequately grounded using the green screw
provided. Ground before attempting to connect
to an electrical power supply.
Do not ground to
a gas supply line.
2.
Wire size must be adequate to minimize voltage
drop during the start-up and operation of the
pump. See Table 2 for recommended wire sizes.
RECOMMENDED MINIMUM WIRE SIZE FOR SHP PUMPS*
Distance from Sub-Panel
0-50 Feet
50-100 Feet
100-150 Feet
150-200 Feet
Pump Model
Inverse - Time Circuit
Breaker or Branch
Fuse AMPs
Class: CC, G, H, J, K,
RK, or T
Voltage
Voltage
Voltage
Voltage
230VAC
115VAC
208-230 VAC 115 VAC 208-230 VAC 115 VAC 208-230 VAC 115 VAC 208-230 VAC 115 VAC
SHPF .50HP/SHPM .75HP
15A
15A
14
12
12
8
10
6
8
6
SHPF .75HP/SHPM 1.0HP
15A
15A
14
12
12
8
10
6
8
6
SHPF 1.0HP/SHPM 1.5HP
15A
20A
12
10
10
8
8
6
6
4
SHPF 1.0-3PH
15A
N/A
14
N/A
12
N/A
10
N/A
8
N/A
SHPF 1.5HP/SHPM 2.0HP
15A
N/A
12
N/A
10
N/A
8
N/A
6
N/A
SHPF 1.5-3PH
15A
N/A
12
N/A
10
N/A
8
N/A
6
N/A
SHPF 2.0HP/SHPM 2.5HP
15A
N/A
12
N/A
8
N/A
6
N/A
6
N/A
SHPF 2.0-3PH
15A
N/A
12
N/A
10
N/A
8
N/A
6
N/A
SHPF 3.0HP
20A
N/A
10
N/A
8
N/A
6
N/A
4
N/A
SHPF 3.0-3PH
15A
N/A
12
N/A
8
N/A
6
N/A
6
N/A
SHPF 5.0
25A
N/A
10
N/A
8
N/A
6
N/A
6
N/A
SHPF 1.0HP-2-SPD (1)
15A
N/A
12
N/A
10
N/A
8
N/A
6
N/A
SHPF 1.5HP-2-SPD (1)
15A
N/A
12
N/A
10
N/A
8
N/A
6
N/A
SHPF 2.0HP-2-SPD (1)
15A
N/A
12
N/A
8
N/A
6
N/A
6
N/A
SHPM 1.5HP-2-SPD (1)
15A
N/A
12
N/A
10
N/A
8
N/A
6
N/A
SHPM 2.0HP-2-SPD (1)
15A
N/A
12
N/A
10
N/A
8
N/A
6
N/A
SHPM 2.5HP-2-SPD (1)
15A
N/A
12
N/A
8
N/A
6
N/A
6
N/A
*Assumes three (3) copper conductors in a buried conduit and 3% maximum voltage loss in branch circuit. All National Electrical Code
®
(NEC
®
) and local codes
must be followed. Table shows minimum wire size and branch fuse recommendations for a typical installation per NEC.
(1) Two-speed pumps are not rated for use with 208 VAC.
Table 2.
Recommended Minimum Wire Size