Page 15
ENGLISH
Jandy
®
Variable-Speed Pumps
|
Installation & Operation Manual
Breaker Panel
Filter Pump Junction Box
Auxillary 1
RS485
Line (in)
Red
Black
Yellow
Green
Load (out)
1 2
Line (in)
Line 1
Load 1
Load 2
Load (out)
1 2
Auxillary 2
Line (in)
Load (out)
1 2
Line (in)
Load (out)
1 2
Auxillary Load
230VAC
External Enclosure
230/115VAC
Supply Power
(GFCI Breaker)
Breaker Panel
230VAC Supply Power
(GFCI Breaker)
Breaker Panel
230VAC Supply Power
(GFCI Breaker)
1 2 3 4
Dry Contacts
1 2 3 4
COM
L1 L2/N
Supply Power Input
Ground
Ground
Load 1
Load 2
Auxillary Load
230VAC
Ground
Dry Contact Speed Settings
Input 1: 3000 RPM
Input 2: 1400 RPM
Input 3: 2200 RPM
Input 4: 1725 RPM
NOTE:
If more than 1 input is shorted to common at the same
time; the motor will run the input with the highest RPM.
DIP Switch
3 4
OFF OFF
Line 2/Neutral
Line 1
Line 1
Line 2
Line 2
Figure 10. 230V Auxiliary Relay Wiring Diagram*
Breaker Panel
Filter Pump Junction Box
Auxillary 1
RS485
Line (in)
Red
Black
Yellow
Green
Load (out)
1 2
Line (in)
Line 1
Load 1
Load 2
Load (out)
1 2
Auxillary 2
Line (in)
Load (out)
1 2
Line (in)
Load (out)
1 2
Auxillary Load
115VAC
External Enclosure
230/115VAC
Supply Power
(GFCI Breaker)
Breaker Panel
115VAC Supply Power
(GFCI Breaker)
Breaker Panel
115VAC Supply Power
(GFCI Breaker)
1 2 3 4
Dry Contacts
1 2 3 4
COM
L1 L2/N
Supply Power Input
Ground
Ground
Load 1
Load 2
Auxillary Load
115VAC
Ground
Dry Contact Speed Settings
Input 1: 3000 RPM
Input 2: 1400 RPM
Input 3: 2200 RPM
Input 4: 1725 RPM
NOTE:
If more than 1 input is shorted to common at the same
time; the motor will run the input with the highest RPM.
DIP Switch
3 4
OFF OFF
Line 1
Line 1
Neutral
Neutral
Line 2/Neutral
Figure 11. 115V Auxiliary Relay Wiring Diagram*
*
WARNING
ELECTRICAL SHOCK HAZARD
Due to the potential risk of fire, electric shock, or injuries to persons, Zodiac
®
Pumps and any auxiliary loads must be installed
in accordance with the National Electrical Code
®
(NEC
®
), all local electrical and safety codes, and the Occupational Safety and
Health Act (OSHA). Copies of the NEC may be ordered from the National Protection Association, 1 Batterymarch Park, Quincy,
MA 02169, or from your local government inspection agency.
In Canada, Zodiac Pumps must be installed in accordance with the Canadian Electrical Code (CEC).
• The Auxiliary Load relay contacts are rated at 230V/115V, 11A RMS. Please ensure the requirements of the equipment to be
connected to the Auxiliary Load
do not exceed this rating
.