5    Safety installations

During the assembly attention must be paid to the safety installations. Only safety parts which are 

tested and labelled for safety may be used. Before setting the boiler into operation make sure that 

all safety installations are in place and belong to the state of the art and work. If necessary check 

them again. Especially the pressure relief valve, the thermal safety relief valve and the expansion 

vessel have to be checked before the boiler is allowed to start running. All safety installations have 

to be checked by an expert every year.

Safety installations are not part of the purchased parts package.

safety relief switch:

The  safety  relief  switch  is  connected  to  the  pellet  burner.  If  the  temperature  of  the  boiler  rises 

above 95°C the safety relief switch stops the burner. The burner will not start on its own if the boiler 

temperature falls below 95°C. You have to reset the switch by hand. Check the water pressure, the 

hydraulic system, especially every pump, the heating controller and the sensors before resetting the 

safety switch (DIN EN 303-5 clause 3.21). 

Please look at chapter 10, too!

thermal safety relief heat exchanger:

The Combiflame has a welded thermal safety relief heat exchanger.

The thermal safety relief heat exchanger may not be used as a domestic hot 

water supply.

 

This heat exchanger has to be used with a thermal safety relief valve which is tested and labelled 

for safety. 

Thermal safety relief valve:

The thermal safety relief valve has to open at 95°C. The assembly of the thermal safety relief valve 

has to be conform to EN 303-5 clause 4.1.5.11.3. The valve must be placed in the cold water supply. 

It is not allowed to have any other valve in front of or behind the safety relief valve. 

!

Make sure that there is always at least 2 bar water pressure in front of the 

thermal safety relief valve. It is not allowed to have any other valve in front 

or behind the safety relief valve! The drain of the thermal safety relief system 

has to be visible. The cross-section of any tubing concerning to the thermal 

safety relief system has to be at least 15 mm.

It is not allowed to set the Combiflame into operation without this safety system! The thermal safety 

relief system has to be installed by an expert and checked every year.

Safety pressure relief valve:

The Combiflame has to be equipped with a pressure safety relief valve which is tested and labelled 

for safety. The maximal system pressure is 3 bar. The drain of the pressure safety relief system has 

to be visible.

Summary of Contents for Combiflame

Page 1: ...Janfire pelletsw rme swedish quality Janfire Combiflame Boiler for wood pellets log and brown coal manual...

Page 2: ...lever on the right side of the boiler After the opening of the flap you have to wait a couple of seconds before you may open the front door 2 Warranty terms The warranty will only be issued on faults...

Page 3: ...n or dirt in the hydraulic system Advanced claims are excluded especially any claim for damages if they are not founded by law If a warranty claim was not justified we will bring our costs to account...

Page 4: ...d this manual Purchased parts package Boiler Combiflame including the catalytic converter four adjustable feet ash pit grill for operation with log pellet burner NH thermal controller for the draft fl...

Page 5: ...23 24 25 26 27 28 connector female screw thread for thermal relief valve flue gas connector muffle 1 for backflow pellet burner thermostat safety relief switch main switch therm relif heat exchanger...

Page 6: ...rn temperature C 55 flue gas average temperature mass flow cross section of flue gas connector average CO2 level in flue gas at nominal heat output average CO level 13 O2 at nominal heat output C g s...

Page 7: ...ief heat exchanger The Combiflame has a welded thermal safety relief heat exchanger The thermal safety relief heat exchanger may not be used as a domestic hot water supply This heat exchanger has to b...

Page 8: ...the maximal operation time adjustable in burner menu a fault message will appear in the display of the burner This case normally happens at the first start running or if you run out of pellets The in...

Page 9: ...ong to the state of the art and work Ask local authorities before installation The heating room has to be conform to the local fire protection requirements If a ventilating system is installed make su...

Page 10: ...r falls below the triggered temperature the burner will start again This kind of regulation is very inefficient and uncomfortable 8 2 2 Modulating operation The burner can be equipped with a modulatio...

Page 11: ...em can be fount in chapter 4 No part of the flue gas system is allowed to be more tighten than the flue gas connector of the boiler A draft regulator is required This regulator is not part of the purc...

Page 12: ...ic cold water supply But it is allowed to operate the boiler with pellets in this case The Combiflame is equipped with a built in thermal safety relief switch conform with EN 303 5 clause 3 21 In case...

Page 13: ...ust them again if necessary 5 Connect the plugs of the burner according to the electric plan The electric connection has to be made according to the local terms by an expert The hose between the auger...

Page 14: ...he connection between burner and auger system and the modulation sensor Open the screw hooks and remove the burner 6 Make sure that the burner and the hose will be stored properly The draft flap has t...

Page 15: ...Start and adjust the burner as said in the manual Make sure that the ash pit is empty and the main heat exchanger and the catalytic converter are clean Do not open any door of the boiler during operat...

Page 16: ...m thick bed of glow Than put the briquette on top of the glow There should be a distance from about 5 cm between the briquettes 3 The front grill has to be covered by the delivered cover sheet start u...

Page 17: ...the front door until you have opened the start up flap by pulling the lever on the right side of the boiler After the opening of the flap you have to wait a couple of seconds before you may open the f...

Page 18: ...an the main heat exchanger an the flue gas system every month cleaning of the grill Never use a vacuum cleaner to clean the grill There is a high risk of fire because of remaining glow Open the bottom...

Page 19: ...mney too 17 Advice to averting of a danger To reduce risk you have to follow all instructions of this manual everytime you use this boiler autumn and spring The natural draft of the chimney depends on...

Page 20: ...door of the boiler has to be kept close Wear fire proved glows any time you open a door during heating Do not open the front door until you have opened the start up flap by pulling the lever on the ri...

Page 21: ...Janfire pelletsw rme swedish quality...

Reviews: