Janitza AHF
60
Menu
Description
System
parameters
Operating modes
There are 12 operating modes available,
Mode 3 (internal)
See section 4.1.3 for details
Start mode
Is used for setting the power on mode of the AHF.
“Auto” mode: The AHF automatically compensates the load
harmonics current.
“Manual” mode starts the compensation only once the
power on command has been received (Power ON).
Transformer position
Grid or load side
Total current
Total current of the system
Compensation mode
2)
Intelligent mode, sequential mode or “All” mode
CT ratio
2)
Ratio of an external current transformer, e.g. 600:5 etc.
Phase angle
2)
Correction of the phase angle of the compensation current
Target voltage
2)
Symmetry function of the mains voltage
Ext. passive filter
2)
Reserve function
VT ratio
2)
Reserve function
THDU limit
2)
Alarm monitoring threshold for THDU
Imbal. limit
2)
Alarm monitoring threshold for imbalance
Derating coeff.
2)
Ratio between the needed and the actual compensation
current
3rd to 13th harmonic
angle
2)
Correction of the phase angle for the respective harmonic
angle
Temperature Derating
2)
On or off – Parameter of the internal control circuit. The
larger the parameter, the greater the stability.
(not configurable)
Capacitive
Compensation
2)
On or off (not configurable)
Mains voltage
Adaptation
2)
On or off (not configurable)
Voltage
Upper limit (%)
2)
If the voltage exceeds the upper threshold -> inductive
comp.
Voltage
Lower limit (%)
2)
If the voltage drops below the lower threshold -> capacitive
comp.
Current transformer
connection
2)
Serial or parallel
Choke config.
2)
Capacitive, inductive, auto-aging (automatic)
Comp. rate
2)
Set the harmonic compensation component; 1.0 shows
100%, etc.
Target cos phi
2)
Desired cos phi
Constant reactive
power
2)
Constant reactive power compensation is needed
2)
The parameters marked in gray are factory set and can only be
changed in consultation with a Janitza service technician