Janitza AHF
80
Technical data
AHF-LCD W 400 V 25 A
AHF-LCD W 400 V 35 A
AHF-LCD W 400 V 50 A
AHF-LCD W 400 V 60 A
AHF-LCD W 400 V 75 A
AHF-LCD W 400 V 100 A
AHF-LCD W 400 V 150 A
Compensation current
25 A
35 A
50 A
60 A
75 A
100 A
150 A
Cooling air requirement
270 m
3
/h
550 m
3
/h
1080 m
3
/h
1500 m
3
/h
Weight
18 kg
35 kg
36 kg
48 kg
Low-voltage HRC outgoing circuit fuse
(on site)
63 A
100 A
160 A
200 A
Nominal voltage
380/415 V (-40% / + 10%)
Nominal frequency
50/60 Hz (frequency range: 45 ... 62 Hz)
Connection
3-phase with or without N-conductor
Harmonic compensation
FFT and intelligent FFT from the 2nd to the 50th harmonic
Reactive current compensation
Dynamic inductive to capacitive, configurable up to 1.0
Load current balancing
ON/ OFF (phase - phase+ phase - N)
Degree of efficiency
≥ 97%
Response time
< 50 µs
Correction time
< 5 ms (10% to 90% filter function)
Expandability
As desired
Inverter
IGBT, 3-level topology
Clock frequency
20 ... 35 kHz
Configuration
Via 4.3” touch display
Communication interface
RS-485 - Modbus RTU
Communication protocol
Modbus protocol, TCP/IP
Measured value acquisition
3-phase measurement of the mains current by means of current transformer
Design
Wall housing, feed from the top
Paint
RAL 9004 black
Protection level
IP20 for indoors
Ambient temperature
+40 °C max. value for brief periods (derating as of 45 °C), +35 °C 24-hour average, -10 °C
lowest value
Relative humidity
Max. 95%, no condensation
Storage temperature
-40 °C to 70 °C
Noise level
< 56 dB
Documentation
User manual in English
AHF-LCD W 400 V – Wall mounted version
Appendix 2 – Technical data